Parameter Name / value range / [default seng] Info
0x2323
(P509.00)
Modbus switch posion
(Modbus switch)
Read only
Display of the DIP switch seng at the last mains power-on.
The value displayed corresponds to the sum of all DIP switch values
(except for DIP switches for terminang resistor).
9.5.3 Baud rate seng
All network nodes must be set to the same baud rate.
Details
If the DIP switch labelled with "b" is in the OFF posion at switch-on, the automac baud
rate detecon funcon is acve. If it is in the ON posion, the seng in 0x2321:002
(P510.02)applies instead.
If the automac baud rate detecon funcon is acvated, the rst 5 ... 10 messages are
lost aer switch-on.
The acve baud rate is displayed in 0x2322:002 (P511.02).
Parameter Name / value range / [default seng] Info
0x2321:002
(P510.02)
Modbus sengs: Baud rate
(Modbus se.: Baud rate)
Oponally seng of the baud rate (instead of seng via DIP switch b).
The baud rate set here is only eecve if DIP switch b was set to ON
before mains switching. Otherwise automac baud rate detecon is
acve.
A change in the baud rate only becomes eecve aer a restart of
Modbus communicaon.
If the automac baud rate detecon funcon is acvated, the rst
5 ... 10 messages are lost aer switch-on.
0 Automac
1 2400 bps
2 4800 bps
3 9600 bps
4 19200 bps
5 38400 bps
6 57600 bps
7 115200 bps
0x2323
(P509.00)
Modbus switch posion
(Modbus switch)
Read only
Display of the DIP switch seng at the last mains power-on.
The value displayed corresponds to the sum of all DIP switch values
(except for DIP switches for terminang resistor).
9.5.4 Data format seng
All network nodes must be set to the same data format.
Details
If the DIP switch labelled with "a" is in the OFF posion at switch-on, the automac data
format detecon funcon is acve. If it is in the ON posion, the seng in 0x2321:003
(P510.03)applies instead.
If the automac data format detecon funcon is acvated, the rst 5 ... 10 messages are
lost aer switch-on.
The acve data format is displayed in 0x2322:003 (P511.03).
Parameter Name / value range / [default seng] Info
0x2321:003
(P510.03)
Modbus sengs: Data format
(Modbus se.: Data format)
Denion of the parity and stop bits.
0 Automac Automac data format detecon.
With this seng, the rst 5 ... 10 messages are lost aer switch-on.
1 8, E, 1 8 data bits, even parity, 1 stop bit
2 8, O, 1 8 data bits, odd parity, 1 stop bit
3 8, N, 2 8 data bits, no parity bit, 2 stop bits
4 8, N, 1 8 data bits, no parity bit, 1 stop bit
0x2323
(P509.00)
Modbus switch posion
(Modbus switch)
Read only
Display of the DIP switch seng at the last mains power-on.
The value displayed corresponds to the sum of all DIP switch values
(except for DIP switches for terminang resistor).
Conguring the network
Modbus RTU
Data format seng
283

Table of Contents

Other manuals for Lenze i55AE155F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i55AE155F and is the answer not in the manual?

Lenze i55AE155F Specifications

General IconGeneral
BrandLenze
Modeli55AE155F
CategoryInverter
LanguageEnglish

Related product manuals