9.4.15 Short setup
In the following, the steps required for controlling the inverter via CANopen are described.
Parameterisaon required
1.
Set the CANopen node address.
•
Each network node must be provided with a unique node address.
•
Details: 4Node address seng ^ 260
2.
Set the CANopen baud rate.
•
Default seng: 500 kbps
•
Details: 4Baud rate
seng ^ 261
3.
Oponal: Congure inverter as "mini master".
•
Required if the inialisaon of the CANopen network and the associated status change
from "Pre-Operaonal" to "Operaonal" is not eected by a higher-level host system.
•
Details: 4Congure device as mini master ^ 262
4.
Oponal: Change the response of the inverter to the triggering of the RPDO me monitor-
ing.
•
Default seng: In case of missing RPDOs, an error is triggered.
•
Details: 4Error responses ^ 275
5.
Save parameter sengs: 0x2022:003 (P700.03) = "On / start [1]".
6.
Switch the inverter o and then on again in order that the changed communicaon set-
tings can get eecve.
7.
Program the master so that the following SDO messages are sent to the inverter:
1.
0x2631:037 (P400.37) = 1 (acvate network control)
2.
0x2860:001 (P201.01) = 5 (set network as standard setpoint source)
3.
PDO mapping and conguraon of the process data objects RPDO1 and TPDO1 (see
the secons "RPDO1 mapping" and "TPDO1 mapping").
8.
Control inverter via RPDO1 (and evaluate the current status via TPDO1).
•
For assignment of the control word and setpoint selecon, see secon "RPDO1 map-
ping".
•
For assignment of the status word and actual value output, see secon "TPDO1 map-
ping".
•
Acceleraon 0x2917 (P220.00) and deceleraon 0x2918 (P221.00) can be set/changed
via SDO messages.
In the default seng, the digital input DI1 is assigned with the "Run" funcon. If
the network control is acvated, this funcon serves as "start enable" for start
commands via network. Hence, the digital input DI1 must be set to HIGH level in
order that the motor can be started via network. 4Start / stop motor ^ 531
Conguring the network
CANopen
Short setup
279