Parameter Name / value range / [default seng] Info
0x2917
(P220.00)
Acceleraon me 1
(Accelerat.me 1)
0.0 ... [5.0] ... 3600.0 s
Acceleraon me 1 for the operang mode "MS: Velocity mode".
•
The acceleraon me set refers to the acceleraon from standsll to
the maximum frequency set. In the case of a lower setpoint selecon,
the actual acceleraon me is reduced accordingly.
•
Seng is not eecve in the operang mode 0x6060 (P301.00) =
"CiA: Velocity mode [2]". 4Device prole CiA 402 ^ 469
0x2918
(P221.00)
Deceleraon me 1
(Decelerat.me 1)
0.0 ... [5.0] ... 3600.0 s
Deceleraon me 1 for the operang mode "MS: Velocity mode".
•
The deceleraon me set refers to the deceleraon from the maxi-
mum frequency set to standsll. In the case of a lower actual fre-
quency, the actual deceleraon me is reduced accordingly.
•
Seng is not eecve in the operang mode 0x6060 (P301.00) =
"CiA: Velocity mode [2]". 4Device prole CiA 402 ^ 469
0x2919
(P222.00)
Acceleraon me 2
(Accelerat.me 2)
0.0 ... [5.0] ... 3600.0 s
Acceleraon me 2 for the operang mode "MS: Velocity mode".
•
The acceleraon me set refers to the acceleraon from standsll to
the maximum frequency set. In the case of a lower setpoint selecon,
the actual acceleraon me is reduced accordingly.
•
The acceleraon me 2 is acve if the frequency setpoint (absolute
value) ≥ auto switching threshold 0x291B (P224.00) or the trigger
assigned to the funcon "Acvate ramp 2" in 0x2631:039 (P400.39) =
TRUE.
•
The acceleraon me 2 is also used for changing the MOP setpoint
generated by the "motor potenometer" funcon.
•
Seng is not eecve in the operang mode 0x6060 (P301.00) =
"CiA: Velocity mode [2]". 4Device prole CiA 402 ^ 469
0x291A
(P223.00)
Deceleraon me 2
(Decelerat.me 2)
0.0 ... [5.0] ... 3600.0 s
Deceleraon me 2 for the operang mode "MS: Velocity mode".
•
The deceleraon me set refers to the deceleraon from the maxi-
mum frequency set to standsll. In the case of a lower actual fre-
quency, the actual deceleraon me is reduced accordingly.
•
The deceleraon me 2 is acve if the frequency setpoint (absolute
value) ≥ auto change-over threshold 0x291B (P224.00) or the trigger
assigned to the funcon "Acvate ramp 2" in 0x2631:039 (P400.39) =
TRUE.
•
The deceleraon me 2 is also used for changing the MOP setpoint
generated by the "motor potenometer" funcon.
•
Seng is not eecve in the operang mode 0x6060 (P301.00) =
"CiA: Velocity mode [2]". 4Device prole CiA 402 ^ 469
0x291B
(P224.00)
Auto-changeover threshold of ramp 2
(Ramp 2 thresh.)
0.0 ... [0.0] ... 599.0 Hz
Threshold for the automac change-over to acceleraon me 2 and
deceleraon me 2.
•
The change-over is eected if the frequency setpoint (absolute value)
≥ auto change-over threshold.
•
With the seng 0, the automac change-over funcon is deacvated.
Basic seng
Frequency limits and ramp mes