5.3.2 Basic inverter sengs
Check the following basic sengs of the inverter and adapt them, if required.
Parameter Name / value range / [default seng] Info
0x2540:001
(P208.01)
Mains sengs: Rated mains voltage
(Mains sengs: Mains voltage)
Seng can only be changed if the inverter is inhibi-
ted.
Selecon of the mains voltage for actuang the inverter.
0 230 Ve
1 400 Ve
2 480 Ve
3 120 Ve
10 230 Ve/reduced LU level
0x2838:001
(P203.01)
Start/stop conguraon: Start method
(Start/stop confg: Start method)
Seng can only be changed if the inverter is inhibi-
ted.
Behaviour aer start command.
0 Normal Aer start command, the standard ramps are acve.
Acceleraon me 1 can be set in 0x2917 (P220.00).
Deceleraon me 1 can be set in 0x2918 (P221.00).
1 DC braking Aer start command, the "DC braking" funcon is acve for the me set
in 0x2B84:002 (P704.02).
4DC braking ^ 437
2 Flying restart circuit Aer the start command, the ying restart circuit is acve.
The ying restart funcon makes it possible to restart a coasng motor
during operaon without speed feedback. Synchronicity between the
inverter and motor is coordinated so that the transion to the rotang
motor is eected without jerk at the me of connecon.
4Flying restart circuit ^ 481
3 Start with magnesaon
0x2838:002
(P203.02)
Start/stop conguraon: Start at power-up
(Start/stop confg: Start at powerup)
Starng performance aer switching on the mains voltage.
0 O No automac start aer switching on mains voltage. In addion to the
inverter enable, a renewed start command is always required to start the
motor.
1 On Automac start of the motor aer switching on the mains voltage if the
inverter is enabled and a start command exists.
0x2838:003
(P203.03)
Start/stop conguraon: Stop method
(Start/stop confg: Stop method)
Behaviour aer the "Stop" command.
0 Coasng The motor becomes torqueless (coasts down to standsll).
1 Standard ramp The motor is brought to a standsll with deceleraon me 1 (or deceler-
aon me 2, if acvated).
Deceleraon me 1 can be set in 0x2918 (P221.00).
Deceleraon me 2 can be set in 0x291A (P223.00).
4Frequency limits and ramp mes ^ 156
2 Quick stop ramp The motor is brought to a standsll with the deceleraon me set for
the "Quick stop" funcon.
Deceleraon me for quick stop can be set in 0x291C (P225.00).
The "quick stop" funcon can also be acvated manually, for instance
via a digital input. 4Quick stop ^ 159
0x283A
(P304.00)
Limitaon of rotaon
(Limit. rotaon)
Oponal restricon of the rotang direcon.
0 Only clockwise (CW) The motor can only be rotated clockwise (CW). The transfer of negave
frequency and PID setpoints to the motor control is prevented.
This funcon takes eect aer the "Reverse rotaonal direcon" func-
on (0x2631:013 (P400.13)).
Since this funcon only prevents negave setpoints, counter-clock-
wise rotaon (CCW) is possible if the motor has been wired for this
rotang direcon.
1 Both rotaonal direcons Both direcons of motor rotaon are enabled.
Commissioning
Parameter seng
Basic inverter sengs
78

Table of Contents

Other manuals for Lenze i55AE155F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i55AE155F and is the answer not in the manual?

Lenze i55AE155F Specifications

General IconGeneral
BrandLenze
Modeli55AE155F
CategoryInverter
LanguageEnglish

Related product manuals