5.3.2 Basic inverter sengs
Check the following basic sengs of the inverter and adapt them, if required.
Parameter Name / value range / [default seng] Info
0x2540:001
(P208.01)
Mains sengs: Rated mains voltage
(Mains sengs: Mains voltage)
•
Seng can only be changed if the inverter is inhibi-
ted.
Selecon of the mains voltage for actuang the inverter.
0 230 Ve
1 400 Ve
2 480 Ve
3 120 Ve
10 230 Ve/reduced LU level
0x2838:001
(P203.01)
Start/stop conguraon: Start method
(Start/stop confg: Start method)
•
Seng can only be changed if the inverter is inhibi-
ted.
Behaviour aer start command.
0 Normal Aer start command, the standard ramps are acve.
•
Acceleraon me 1 can be set in 0x2917 (P220.00).
•
Deceleraon me 1 can be set in 0x2918 (P221.00).
1 DC braking Aer start command, the "DC braking" funcon is acve for the me set
in 0x2B84:002 (P704.02).
4DC braking ^ 437
2 Flying restart circuit Aer the start command, the ying restart circuit is acve.
The ying restart funcon makes it possible to restart a coasng motor
during operaon without speed feedback. Synchronicity between the
inverter and motor is coordinated so that the transion to the rotang
motor is eected without jerk at the me of connecon.
4Flying restart circuit ^ 481
3 Start with magnesaon
0x2838:002
(P203.02)
Start/stop conguraon: Start at power-up
(Start/stop confg: Start at powerup)
Starng performance aer switching on the mains voltage.
0 O No automac start aer switching on mains voltage. In addion to the
inverter enable, a renewed start command is always required to start the
motor.
1 On Automac start of the motor aer switching on the mains voltage if the
inverter is enabled and a start command exists.
0x2838:003
(P203.03)
Start/stop conguraon: Stop method
(Start/stop confg: Stop method)
Behaviour aer the "Stop" command.
0 Coasng The motor becomes torqueless (coasts down to standsll).
1 Standard ramp The motor is brought to a standsll with deceleraon me 1 (or deceler-
aon me 2, if acvated).
•
Deceleraon me 1 can be set in 0x2918 (P221.00).
•
Deceleraon me 2 can be set in 0x291A (P223.00).
4Frequency limits and ramp mes ^ 156
2 Quick stop ramp The motor is brought to a standsll with the deceleraon me set for
the "Quick stop" funcon.
•
Deceleraon me for quick stop can be set in 0x291C (P225.00).
•
The "quick stop" funcon can also be acvated manually, for instance
via a digital input. 4Quick stop ^ 159
0x283A
(P304.00)
Limitaon of rotaon
(Limit. rotaon)
Oponal restricon of the rotang direcon.
0 Only clockwise (CW) The motor can only be rotated clockwise (CW). The transfer of negave
frequency and PID setpoints to the motor control is prevented.
•
This funcon takes eect aer the "Reverse rotaonal direcon" func-
on (0x2631:013 (P400.13)).
•
Since this funcon only prevents negave setpoints, counter-clock-
wise rotaon (CCW) is possible if the motor has been wired for this
rotang direcon.
1 Both rotaonal direcons Both direcons of motor rotaon are enabled.
Commissioning
Parameter seng
Basic inverter sengs
78