8.2.1.1 Linear V/f characterisc
The linear V/f characterisc is the most used characterisc shape for general applicaons
since they cause a torque that is largely constant.
Details
Select V/f characterisc control with linear characterisc:
1.
Motor control mode 0x2C00 (P300.00) = "V/f characterisc control (VFC open loop) [6]"
2.
V/f characterisc shape 0x2B00 (P302.00) = "Linear [0]"
Seng of the V/f characterisc:
•
Liming factors for the V/f characterisc are rated mains voltage 0x2540:001 (P208.01),
minimum frequency 0x2915 (P210.00) and maximum frequency 0x2916 (P211.00).
•
The base voltage 0x2B01:001 (P303.01) is usually set to the rated motor voltage (motor
nameplate data). The base voltage is preset to the rated mains voltage. This again is preset
according to the product key of the inverter. 4Mains voltage ^ 144
•
The base frequency 0x2B01:002 (P303.02) is usually set to the rated motor frequency
(motor nameplate data).
0
[V]
[Hz]
0
0x2B01 001:
0x2B01 002:
0x2540 001:
0x29160x2915
The current output frequency can exceed the set maximum frequency if the
gain for the slip compensaon in 0x2B09:001 (P315.01) is set to a value higher
than 0.
Example
In this example, a 400 V/50 Hz motor is connected to the inverter which is to be operated with
maximally 75 Hz. The minimum frequency is set to 10 Hz.
•
V/f characterisc on the le: The inverter is operated with a rated mains voltage of 400 V.
•
V/f characterisc on the right: The inverter is operated with a rated mains voltage of 480 V.
This causes the output voltage to further increase above 50 Hz.
0
[V]
[Hz]
0
0
[V]
[Hz]
010 50 75 10 50 75
400 400
480
Parameter Name Seng for this example
0x2540:001 (P208.01) Rated mains voltage 400 Ve [1] (on the le) / 480 Ve [2] (on the right)
0x2915 (P210.00) Minimum frequency 10 Hz
0x2916 (P211.00) Maximum frequency 75 Hz
0x2B01:001 (P303.01) Base voltage 400 V
0x2B01:002 (P303.02) Base frequency 50 Hz
Next steps
•
The inverter provides dierent funcons by means of which the drive behaviour can be
further opmised.4Opmisaon of motor control ^ 182
•
An opmisaon of the control loops is not mandatory for this motor control type but may
lead to a
beer control mode. 4Opmisaon of the control loops ^ 193
Motor control
Motor control selecon
V/f characterisc control (VFC)
167