7.3 Control source selecon
The selected "control source" serves to provide the inverter with its start, stop, and reversal
commands.
Possible control sources are:
Digital inputs
Keypad
Network
Irrespecve of the control source selecon, stop commands are always acve
from each source connected! If, for instance, the network control is acve and a
keypad is connected for diagnosc purposes, the motor is also stopped if the
keypad key is pressed.
Excepon: In the jog operaon, a stop command has no impact.
Details
The default seng "Flexible I/O conguraon [0]" in 0x2824 (P200.00) enables a exible
control of the inverter via digital inputs, network and keypad. The control of the inverter
via the digital inputs is precongured. For details see the chapter "Funcon assignment of
the inputs and outputs". ^ 82
If the keypad is to be used as the sole control source for the applicaon, selecon "Keypad
[1]" is to be set in 0x2824 (P200.00).
The control source that is currently acve is displayed in 0x282B:001 (P125.01).
Parameter Name / value range / [default seng] Info
0x2824
(P200.00)
Control selecon
(Control select.)
Selecon of the type of inverter control.
0 Flexible I/O conguraon This selecon enables a exible assignment of the start, stop, and rotat-
ing direcon commands with digital signal sources.
Digital signal sources can be digital inputs, network and keypad.
The I/O conguraon is made via the parameters 0x2631:xx (P400.xx).
1 Keypad This selecon enables the motor to be started exclusively via the start
key of the keypad. Other signal sources for starng the motor are
ignored.
Start motor Stop motor
Note!
The funcons "Enable inverter" 0x2631:001 (P400.01) and "Run"
0x2631:002 (P400.02) must be set to TRUE to start the motor.
If jog operaon is acve, the motor cannot be stopped via the
keypad key.
0x282B:001
(P125.01)
Inverter diagnoscs: Acve control source
(Inverter diag.: Acve control)
Read only
Display of the control source that is currently acve.
0 Flexible I/O conguraon
1 Network
2 Keypad
8 Keypad full control
Related topics
The preset I/O conguraon can be individually adapted to the respecve applicaon. For
details see the chapter "Flexible I/O conguraon". ^ 525
For details of the network control of the inverter, see the chapter "General network set-
tings". ^ 227
Basic seng
Control source selecon
147

Table of Contents

Other manuals for Lenze i55AE155F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i55AE155F and is the answer not in the manual?

Lenze i55AE155F Specifications

General IconGeneral
BrandLenze
Modeli55AE155F
CategoryInverter
LanguageEnglish

Related product manuals