11.2 Keypad
For the keypad various sengs can be made, which are described in detail in the following
subchapters.
11.2.1 Keypad language selecon
Parameter Name / value range / [default seng] Info
0x2863
(P705.00)
Keypad language selecon
(KP language)
Language selecon for the keypad display.
0 No language selected
1 English
2 German
11.2.2 Keypad setpoint increment
Parameter Name / value range / [default seng] Info
0x2862
(P701.00)
Keypad setpoint increment
(KP setp. incr.)
1 ... [1] ... 100
Adaptaon of the increment for keypad setpoints when a keypad arrow
key is pressed once. The value set serves as a mulplier for the preset
increments.
Preset increments:
•
0.1 Hz for frequency setpoint 0x2601:001 (P202.01).
•
0.01 PUnit for process controller setpoint 0x2601:002 (P202.02).
•
1 % for torque setpoint 0x2601:003 (P202.03).
Notes:
•
With a seng > 1, the opon of repeatedly changing the setpoint by
pressing the key for a longer me is deacvated.
•
The seng only has an impact on the keypad setpoints.
Example: with the seng "5", the keypad frequency setpoint is
increased/decreased by 0.5 Hz every me the key is pressed.
11.2.3 Keypad scaling of speed display
Parameter Name / value range / [default seng] Info
0x4002
(P702.00)
Speed display scaling
(Scal.speed fact.)
0.00 ... [0.00] ... 650.00
Factor for the scaling of the speed display in 0x400D (P101.00).
•
With the seng "0.00", no scaling takes place.
•
Example: with the "16.50" and the actual frequency = 50 Hz, 0x400D
(P101.00) shows the speed "825 rpm".
0x400D
(P101.00)
Scaled actual value
(Scaled act value)
•
Read only: x Units
Display of the current speed in applicaon units.
11.2.4 Keypad status display
During operaon, the keypad displays the output frequency of the inverter, or with an acve
PID control it shows the process controller setpoint. Alternavely, an oponal diagnosc
parameter can be displayed during operaon.
Parameter Name / value range / [default seng] Info
0x2864
(P703.00)
Keypad status display
(KP status displ.)
0x00000000 ... [0x00000000] ... 0xFFFFFF00
0 = normal display depending on the operang mode
•
In case of an acve frequency control, the keypad displays the output
frequency of the inverter.
•
In case of acve PID control, the keypad displays the current Process
controller setpoint in [P-Unit].
As an alternave, an oponal diagnosc parameter can be set here,
which is to be shown on the keypad during operaon.
•
Format: 0xiiiiss00 (iiii = hexadecimal index, ss = hexadecimal subindex)
•
The lowest byte is always 0x00.
•
The keypad can be used to select the desired diagnoscs parameter
from a list.
Addional funcons
Keypad
Keypad status display
422