11.7 Access protecon
11.7.1 Write access protecon
Oponally a write access protecon can be installed for the inverter parameters.
Write access protecon only restricts parameterisaon via keypad and »EASY
Starter«. Write access protecon via network is not restricted. Irrespecve of
the write access protecon that is currently set, a higher-level controller, OPC-
UA server, or any other communicaon partner connected to the inverter is
always provided with full read/write access to all parameters of the inverter.
Aer acvang the write access protecon, you have to enter a valid PIN to
remove the write access protecon. Note down the dened PIN(s) and keep this
informaon in a safe place! If you lose the PIN(s), the inverter can only be disa-
bled by reseng it to the delivery status. This means, all parameter sengs
made by the user get lost! 4Reset parameters to default ^ 418
Details
Usually the write access protecon funcon is implemented by the mechanical engineer/
OEM , for example to protect the inverter against incorrect parameterisaon by non-author-
ised persons. For diagnosc purposes, a read access to all parameters is always possible.
The write access protecon allows for the following conguraons:
•
Full write access
•
Write access only to favorites or (when knowing PIN1) to all parameters
•
No write access or (when knowing PIN2) full write access
•
No write access or (when knowing PIN1) write access only to favorites or (when knowing
PIN2) to all parameters
The following table compares the four possible conguraons:
PIN1 seng PIN2 seng Log-in Status display aer
log-in
Acve write access protecon (via keypad/»EASY Starter«)
0x203D (P730.00) 0x203E (P731.00) 0x203F 0x2040 (P197.00)
0 0 - 0 No access protecon congured.
All parameters
Favorites
Diagnostics (read access)
Access
> 0 0 0 or wrong PIN 2 Write access only possible to favorites.
Correct PIN1 0 Write access to all parameters possible.
Access
PIN1
All parameters
Favorites
Diagnostics (read access)
0 > 0 0 or wrong PIN 1 No write access.
Correct PIN2 0 Write access to all parameters possible.
Access
PIN2
All parameters
Favorites
Diagnostics (read access)
> 0 > 0 0 or wrong PIN 1 No write access.
Correct PIN1 2 Write access only possible to favorites.
Correct PIN2 0 Write access to all parameters possible.
Access
PIN2PIN1
All parameters
Favorites
Diagnostics (read access)
If PIN1 and PIN2 are set idencally, a write access to all parameters is possible aer the PIN has been
entered correctly.
Addional funcons
Access protecon
Write access protecon