11.9 Parameter change-over
For up to 32 freely selectable parameters, this funcon provides a change-over between four
sets with dierent parameter values.
DANGER!
Changed parameter sengs are eecve immediately.
The possible consequence is an unexpected response of the motor sha while the inverter is
enabled.
▶
If possible, only carry out parameter changes while the inverter is disabled.
▶
Certain device commands or sengs which might cause a crical state of the drive behav-
iour can generally only be carried our when the inverter is inhibited.
Details
The parameter list is compiled in the same way as that of the "Favorites" via congura-
on. »EASY Starter« provides a user-friendly parameterisaon dialog for this purpose.
Change-over to another value set can oponally be eected via corresponding device com-
mands and/or special funcons/triggers:
4Device commands for parameter change-over ^ 421
4Funcons for parameter change-over ^ 579
Parameter Name / value range / [default seng] Info
0x2022:011
(P700.11)
Device commands: Save parameter set 1
(Device commands: Save par. set 1)
•
For further possible sengs, see parameter
0x2022:001 (P700.01). ^ 418
1 = save value set 1 of the "Parameter change-over" funcon.
•
When the device command has been executed successfully, the value
0 is shown.
0 O / ready
0x2022:012
(P700.12)
Device commands: Save parameter set 2
(Device commands: Save par. set 2)
•
For further possible sengs, see parameter
0x2022:001 (P700.01). ^ 418
1 = save value set 2 of the "Parameter change-over" funcon.
•
When the device command has been executed successfully, the value
0 is shown.
0 O / ready
0x2022:013
(P700.13)
Device commands: Save parameter set 3
(Device commands: Save par. set 3)
•
For further possible sengs, see parameter
0x2022:001 (P700.01). ^ 418
1 = save value set 3 of the "Parameter change-over" funcon.
•
When the device command has been executed successfully, the value
0 is shown.
0 O / ready
0x2022:014
(P700.14)
Device commands: Save parameter set 4
(Device commands: Save par. set 4)
•
For further possible sengs, see parameter
0x2022:001 (P700.01). ^ 418
0 O / ready
0x4041:001 ...
0x4041:032
(P750.01 ... 32)
Parameter change-over: Parameter 1 ... Parameter 32
(Param.set setup: Parameter 1 ... Parameter 32)
0x00000000 ... [0x00000000] ... 0xFFFFFF00
Denion of the parameter list for the "Parameter change-over" func-
on.
•
Format: 0xiiiiss00 (iiii = hexadecimal index, ss = hexadecimal subindex)
•
The lowest byte is always 0x00.
0x4042:001 ...
0x4042:032
(P751.01 ... 32)
Parameter value set 1: Value of parameter 1 ... Value
of parameter 32
(Par. value set 1: Set 1 - Value 1 ... Set 1 - Value 32)
-2147483648 ... [0] ... 2147483647
Value set 1 for the parameter list dened in 0x4041:001 ... 0x4041:032
(P750.01 ... 32).
0x4043:001 ...
0x4043:032
(P752.01 ... 32)
Parameter value set 2: Value of parameter 1 ... Value
of parameter 32
(Par. value set 2: Set 2 - Value 1 ... Set 2 - Value 32)
-2147483648 ... [0] ... 2147483647
Value set 2 for the parameter list dened in 0x4041:001 ... 0x4041:032
(P750.01 ... 32).
0x4044:001 ...
0x4044:032
(P753.01 ... 32)
Parameter value set 3: Value of parameter 1 ... Value
of parameter 32
(Par. value set 3: Set 3 - Value 1 ... Set 3 - Value 32)
-2147483648 ... [0] ... 2147483647
Value set 3 for the parameter list dened in 0x4041:001 ... 0x4041:032
(P750.01 ... 32).