Parameter Name / value range / [default seng] Info
0x4016:005 Digital output 1: Terminal state
•
Read only
Display of the logic state of output terminal X3/DO1.
0 FALSE
1 TRUE
0x4016:006 Digital output 1: Trigger signal state
•
Read only
Display of the logic state of the trigger signal for digital output 1 (without
taking a ON/OFF delay set and inversion into consideraon).
0 FALSE
1 TRUE
0x4017:005 Digital output 2: Terminal state
•
Read only
•
Only available for applicaon I/O.
Display of the logic state of output terminal X3/DO2.
0 FALSE
1 TRUE
0x4017:006 Digital output 2: Trigger signal state
•
Read only
•
Only available for applicaon I/O.
Display of the logic state of the trigger signal for digital output 2 (without
taking a ON/OFF delay set and inversion into consideraon).
0 FALSE
1 TRUE
0x4018:005 Relay: Relay state
•
Read only
Display of the logic state of the relay.
0 FALSE
1 TRUE
0x4018:006 Relay: Trigger signal state
•
Read only
Display of the logic state of the trigger signal for the relay (without tak-
ing a ON/OFF delay set and inversion into consideraon).
0 FALSE
1 TRUE
Related topics
4Conguraon of digital inputs ^ 594
4Conguraon of digital outputs ^ 603
6.2.5.2 Analog inputs and outputs
The following parameters serve to diagnose the analog inputs and outputs of the inverter.
Parameter Name / value range / [default seng] Info
0x2DA4:001
(P110.01)
Diagnoscs of analog input 1: Value in percent
(AI1 diagnoscs: AI1 terminal %)
•
Read only: x.x %
Display of the current input value at X3/AI1 scaled as value in percent.
•
100 % ≡ 10 V or 20 mA or 5 V
0x2DA4:002
(P110.02)
Diagnoscs of analog input 1: Frequency value
(AI1 diagnoscs: AI1 scaled freq.)
•
Read only: x.x Hz
Display of the current input value at X3/AI1 scaled as a frequency value.
•
The standard setpoint source for operang mode 0x6060 (P301.00) =
"MS: Velocity mode [-2]" is selected in 0x2860:001 (P201.01).
0x2DA4:003
(P110.03)
Diagnoscs of analog input 1: Process controller value
(AI1 diagnoscs: AI1 scaled PID)
•
Read only: x.xx PID unit
Display of the current input value at X3/AI1 scaled as a process controller
value.
•
The standard setpoint source for the reference value of PID control is
selected in 0x2860:002 (P201.02).
0x2DA4:004
(P110.04)
Diagnoscs of analog input 1: Torque value
(AI1 diagnoscs: AI1 scaled torq.)
•
Read only: x.x %
Display of the current input value at X3/AI1 scaled as a percentage tor-
que value.
•
100 % ≡ permissible maximum torque 0x6072 (P326.00)
•
The standard setpoint source for operang mode 0x6060 (P301.00) =
"MS: Torque mode [-1]" is selected in 0x2860:003 (P201.03).
Diagnoscs and fault eliminaon
Diagnoscs parameter
Diagnoscs of the inputs and outputs