Parameter Name / value range / [default seng] Info
0x2860:002
(P201.02)
PID control: Default setpoint source
(Stnd. setpoints: PID setp. src.)
Selecon of the standard setpoint source for the reference value of the
PID control.
•
The selected standard setpoint source is always acve with an acva-
ted PID control when no setpoint change-over to another setpoint
source via corresponding triggers/funcons is acve.
1 Keypad The setpoint is specied locally by the keypad.
•
Default seng: 0x2601:002 (P202.02)
•
Use the and navigaon keys to change the keypad setpoint
(also during running operaon).
2 Analog input 1 The setpoint is dened as analog signal via the analog input 1.
4Analog input 1 ^ 597
3 Analog input 2 The setpoint is dened as analog signal via the analog input 2.
4Analog input 2 ^ 601
4 HTL input (from version 04.00) The digital inputs DI3 and DI4 can be congured as HTL input to use an
HTL encoder as setpoint encoder or dene the setpoint as a reference
frequency ("pulse train").
4HTL input setpoint source ^ 565
5 Network The setpoint is dened as process data object via the network.
4Conguring the network ^ 226
11 PID preset 1 For the setpoint selecon, preset values can be parameterised and selec-
ted.
4Setpoint source of preset setpoints ^ 554
12 PID preset 2
13 PID preset 3
14 PID preset 4
15 PID preset 5
16 PID preset 6
17 PID preset 7
18 PID preset 8
31 Segment preset 1 (from version 03.00) For the setpoint selecon, the segment presets parameterised for the
"sequencer" funcon can be selected as well.
4Sequencer ^ 504
32 Segment preset 2 (from version 03.00)
33 Segment preset 3 (from version 03.00)
34 Segment preset 4 (from version 03.00)
35 Segment preset 5 (from version 03.00)
36 Segment preset 6 (from version 03.00)
37 Segment preset 7 (from version 03.00)
38 Segment preset 8 (from version 03.00)
50 Motor potenometer The setpoint is generated by the "motor potenometer" funcon. This
funcon can be used as an alternave setpoint control which is control-
led via two signals: "MOP setpoint up" and "MOP setpoint down".
4Motor potenometer setpoint source (MOP) ^ 559
201 Internal value (from version 05.00) Internal values of the manufacturer.
202 Internal value (from version 05.00)
203 Internal value (from version 05.00)
204 Internal value (from version 05.00)
205 Internal value (from version 05.00)
206 Internal value (from version 05.00)
Basic seng
Selecon of setpoint source
150