Parameter Name / value range / [default seng] Info
0x2860:002
(P201.02)
PID control: Default setpoint source
(Stnd. setpoints: PID setp. src.)
Selecon of the standard setpoint source for the reference value of the
PID control.
The selected standard setpoint source is always acve with an acva-
ted PID control when no setpoint change-over to another setpoint
source via corresponding triggers/funcons is acve.
1 Keypad The setpoint is specied locally by the keypad.
Default seng: 0x2601:002 (P202.02)
Use the and navigaon keys to change the keypad setpoint
(also during running operaon).
2 Analog input 1 The setpoint is dened as analog signal via the analog input 1.
4Analog input 1 ^ 597
3 Analog input 2 The setpoint is dened as analog signal via the analog input 2.
4Analog input 2 ^ 601
4 HTL input (from version 04.00) The digital inputs DI3 and DI4 can be congured as HTL input to use an
HTL encoder as setpoint encoder or dene the setpoint as a reference
frequency ("pulse train").
4HTL input setpoint source ^ 565
5 Network The setpoint is dened as process data object via the network.
4Conguring the network ^ 226
11 PID preset 1 For the setpoint selecon, preset values can be parameterised and selec-
ted.
4Setpoint source of preset setpoints ^ 554
12 PID preset 2
13 PID preset 3
14 PID preset 4
15 PID preset 5
16 PID preset 6
17 PID preset 7
18 PID preset 8
31 Segment preset 1 (from version 03.00) For the setpoint selecon, the segment presets parameterised for the
"sequencer" funcon can be selected as well.
4Sequencer ^ 504
32 Segment preset 2 (from version 03.00)
33 Segment preset 3 (from version 03.00)
34 Segment preset 4 (from version 03.00)
35 Segment preset 5 (from version 03.00)
36 Segment preset 6 (from version 03.00)
37 Segment preset 7 (from version 03.00)
38 Segment preset 8 (from version 03.00)
50 Motor potenometer The setpoint is generated by the "motor potenometer" funcon. This
funcon can be used as an alternave setpoint control which is control-
led via two signals: "MOP setpoint up" and "MOP setpoint down".
4Motor potenometer setpoint source (MOP) ^ 559
201 Internal value (from version 05.00) Internal values of the manufacturer.
202 Internal value (from version 05.00)
203 Internal value (from version 05.00)
204 Internal value (from version 05.00)
205 Internal value (from version 05.00)
206 Internal value (from version 05.00)
Basic seng
Selecon of setpoint source
150

Table of Contents

Other manuals for Lenze i55AE155F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i55AE155F and is the answer not in the manual?

Lenze i55AE155F Specifications

General IconGeneral
BrandLenze
Modeli55AE155F
CategoryInverter
LanguageEnglish

Related product manuals