EasyManuals Logo
Home>Lenze>Inverter>i55AE155F

Lenze i55AE155F User Manual

Lenze i55AE155F
702 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #53 background imageLoading...
Page #53 background image
4.2.6.2 Fusing and terminal data
Fuse data
Inverter I55AE137F
I55AE155F
I55AE175F
I55AE211F
I55AE215F
I55AE222F
I55AE230F
I55AE240F
I55AE255F
I55AE275F
I55AE311F
Cable installaon in compliance with EN 60204-1
Installaon method B2
operaon without mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 10 16 25 32
Circuit breaker
Characteriscs B
Max. rated current A 10 16 25 32
operaon with mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 10 16 25 32
Circuit breaker
Characteriscs B
Max. rated current A 10 16 25 32
Earth-leakage circuit breaker
3-phase mains connecon ≥ 30 mA, type B ≥ 300 mA, type B
Fuse data
Inverter I55AE315F
I55AE318F
I55AE322F
I55AE330F I55AE337F I55AE345F
Cable installaon in compliance with EN 60204-1
Installaon method B2 C
operaon without mains choke
Fuse
Characteriscs gG/gL or gRL -
Max. rated current A 63 - - -
Circuit breaker
Characteriscs B -
Max. rated current A 63 - - -
operaon with mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 63 80 100 125
Circuit breaker
Characteriscs B
Max. rated current A 63 80 100 125
Earth-leakage circuit breaker
3-phase mains connecon ≥ 300 mA, type B
Electrical installaon
Mains connecon
3-phase mains connecon 480 V
53

Table of Contents

Other manuals for Lenze i55AE155F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i55AE155F and is the answer not in the manual?

Lenze i55AE155F Specifications

General IconGeneral
BrandLenze
Modeli55AE155F
CategoryInverter
LanguageEnglish

Related product manuals