9.2.5 Parameter access monitoring (PAM)
The parameter access monitoring can be used as basic protecon against a control loss of the
inverter. Monitoring is triggered if a parameter write access to a certain index does not take
place at regular intervals via the established communicaon connecon.
Precondions
This monitoring only works when the network control is acvated.
Except for the keypad, the monitoring can be used for all communicaon connecons, for
instance:
PC/Engineering Tool <--> inverter with USB module
PC/Engineering Tool <--> inverter with WLAN module
Controller <--> network <--> inverter with network opon
Details
For monitoring purposes, a non-zero value must be wrien into the "Keep-alive register"
0x2552:002 (P595.02) at regular intervals. The rst write access with a non-zero value ac-
vates monitoring. The intervals between the write accesses must not be higher than the me-
out me set in 0x2552:003 (P595.03). If no parameter write access takes place within the
me-out me, monitoring is triggered: The response selected in 0x2552:005 (P595.05) takes
place and the acon selected in 0x2552:005 (P595.05). In addion, the status bit 1 in
0x2552:006 (P595.06) is set to "1".
The error status can be le by a normal "error reset". Since monitoring connues to be acve
and the me-out me is not reset by the error reset, the inverter immediately changes again
to the error status. In order to prevent his, you have the following opons:
a)
Restore communicaon exchange.
b)
Set the monitoring response in 0x2552:004 (P595.04) to "No response [0]" or "Warning
[1]".
c)
Change over to local or exible control.
Parameter Name / value range / [default seng] Info
0x2552:002
(P595.02)
Parameter access monitoring: Keep alive register
(PAM monitoring: Keep alive reg.)
0 ... [0] ... 65535
From version 04.00
Register for cyclic parameter write accesses for monitoring the commu-
nicaon link.
If the seng is non-zero, the monitoring is acve.
In order that the monitoring is not tripped, a non-zero value has to be
entered into this index at regular intervals. The temporal distances of
the write accesses must not be higher than the me-out me set in
0x2552:003 (P595.03).
0x2552:003
(P595.03)
Parameter access monitoring: Time-out me
(PAM monitoring: Time-out me)
0.0 ... [10.0] ... 6553.5 s
From version 04.00
Maximum permied me between two write accesses to the "keep-
alive-register".
In case of a me-out
the error response selected in 0x2552:004 (P595.04) is eected,
the acon selected in 0x2552:005 (P595.05) is eected,
the status bit 1 in 0x2552:006 (P595.06) is set to "1".
0x2552:004
(P595.04)
Parameter access monitoring: Reacon
(PAM monitoring: Reacon)
From version 04.00
For further possible sengs, see parameter
0x2D45:001 (P310.01). ^ 223
Selecon of the response to the triggering of the parameter access mon-
itoring.
Associated error code:
33045 | 0x8115 - Time-out (PZÜ)
0 No response
0x2552:005
(P595.05)
Parameter access monitoring: Acon
(PAM monitoring: Acon)
From version 04.00
Selecon of the acon to be executed if the parameter access monitor-
ing is triggered.
0 No acon
1 Reserved
Conguring the network
Predened process data words
Parameter access monitoring (PAM)
257

Table of Contents

Other manuals for Lenze i55AE155F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i55AE155F and is the answer not in the manual?

Lenze i55AE155F Specifications

General IconGeneral
BrandLenze
Modeli55AE155F
CategoryInverter
LanguageEnglish

Related product manuals