33045 0x8115 Time-out (PZÜ) Keypad display: Time-out (PAM)
Cause Error type/response Remedy
The parameter access monitoring (PAM) func-
on has been acvated. For a me longer than
the me-out period set in 0x2552:003
(P595.03), no value was entered into the "Keep-
alive-Register" 0x2552:002 (P595.02).
No response
•
The error type can be congured in
0x2552:004 (P595.04).
•
Check communicaon.
•
Check sengs of the parameter access moni-
toring (PAM) funcon.
Related topics
4Parameter access monitoring (PAM) ^ 257
33046 0x8116 Modbus TCP master me-out Keypad display: MBTCP mast t-out
Cause Error type/response Remedy
No valid messages have been received by the
Modbus master for a me longer than the me-
out period set in 0x23B6:001 (P514.01).
Fault
•
The error type can be congured in
0x2859:008 (P515.08).
Check communicaon with the master.
Related topics
4Time-out behaviour ^ 351
33047 0x8117 Modbus TCP Keep Alive me-out Keypad display: MB.Keep Alive TO
Cause Error type/response Remedy
For a me longer than the me-out period set
in 0x23B6:002 (P514.02), no value was entered
into the Keep alive register 0x23B6:005
(P514.05).
Fault
•
The error type can be congured in
0x2859:009 (P515.09).
Check communicaon with the master.
Related topics
4Time-out behaviour ^ 351
33154 0x8182 CAN: bus o Keypad display: CAN bus o
Cause Error type/response Remedy
Too many faulty frames have been received.
•
Defecve cable (e. g. loose contact).
•
Two nodes with the same node address.
Trouble
•
Change to the "Bus-O" communicaon sta-
tus.
•
The error type can be congured in
0x2857:010.
•
Check wiring of the network.
•
Check bus terminang resistor.
•
Set the idencal baud rate for each node of
the network.
•
Assign a unique node address to each node
of the network.
•
Eliminate EMC interferences.
33155 0x8183 CAN: warning Keypad display: CAN bus warning
Cause Error type/response Remedy
Too many faulty frames have been received.
•
Defecve cable (e. g. loose contact).
•
Two nodes with the same node address.
Warning
•
The error type can be congured in
0x2857:011.
•
Check wiring of the network.
•
Check bus terminang resistor.
•
Set the idencal baud rate for each node of
the network.
•
Assign a unique node address to each node
of the network.
•
Eliminate EMC interferences.
Appendix
Error codes
652