Response aer inial switch-on of the inverter
Aer switch-on, the inverter rst tries to load the parameter sengs stored in the user mem-
ory. If the user memory is empty or damaged, an error message is output and the user must
intervene:
Opon 1 = user memory empty: → default seng is loaded automacally from the rm-
ware → data are saved automacally in the user memory of the memory module.
Opon 2 = user- memory damaged: → Error message → default seng is loaded automat-
ically → data are saved automacally in the user memory of the memory module.
Opon 3 = OEM memory empty/damaged: → error message → data are loaded automa-
cally from the user memory of the memory module.
Parameter Name / value range / [default seng] Info
0x2022:003
(P700.03)
Device commands: Save user data
(Device commands: Save user data)
For further possible sengs, see parameter
0x2022:001 (P700.01). ^ 418
1 = save current parameter sengs in the main memory of the memory
module with mains failure protecon.
It may take some seconds to execute the task. When the task has
been executed successfully, the value 0 is shown.
Do not switch o the supply voltage during the saving process and do
not unplug the memory module from the inverter!
When the inverter is switched on, all parameters are automacally
loaded from the main memory of the memory module to the RAM
memory of the inverter.
0 O / ready
0x2022:004
(P700.04)
Device commands: Load user data
(Device commands: Load user data)
Seng can only be changed if the inverter is inhibi-
ted.
For further possible sengs, see parameter
0x2022:001 (P700.01). ^ 418
1 = load data from the main memory of the memory module to the RAM
memory of the inverter.
When the device command has been executed successfully, the value
0 is shown.
Loading parameters has a direct eect on the cyclic communicaon:
The data exchange for control is interrupted and a communicaon
error is generated.
0 O / ready
0x2022:005
(P700.05)
Device commands: Load OEM data
(Device commands: Load OEM data)
Seng can only be changed if the inverter is inhibi-
ted.
For further possible sengs, see parameter
0x2022:001 (P700.01). ^ 418
1 = load data from the OEM memory of the memory module to the RAM
memory of the inverter.
When the device command has been executed successfully, the value
0 is shown.
Loading parameters has a direct eect on the cyclic communicaon:
The data exchange for control is interrupted and a communicaon
error is generated.
0 O / ready
0x2022:006
(P700.06)
Device commands: Save OEM data
(Device commands: Save OEM data)
For further possible sengs, see parameter
0x2022:001 (P700.01). ^ 418
1 = save current parameter sengs in the OEM memory of the memory
module with mains failure protecon.
At the same me, the parameter sengs are saved in the main mem-
ory of the memory module.
Aer successful execuon, the value 0 is shown.
0 O / ready
0x2829
(P732.00)
Automac storage in the memory module
(Auto-Save EPM)
1 = acvate automac saving of parameters in the memory module.
With the seng 0, the "Save user data" 0x2022:003 (P700.03) device
command must be explicitly executed, or the "Enter" keypad key must
be pressed for longer than 3 s to save the current parameter sengs
in the memory module of the inverter with mains failure protecon.
0 Inhibit
1 Enable
Related topics
4Data handling ^ 141
Addional funcons
Device Commands
Saving/loading the parameter sengs
420

Table of Contents

Other manuals for Lenze i55AE155F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i55AE155F and is the answer not in the manual?

Lenze i55AE155F Specifications

General IconGeneral
BrandLenze
Modeli55AE155F
CategoryInverter
LanguageEnglish

Related product manuals