Fuse data
Inverter I55AE125B
I55AE137B
I55AE155B
I55AE175B
I55AE125D
I55AE137D
I55AE155D
I55AE175D
I55AE211B
I55AE215B
I55AE222B
I55AE211D
I55AE215D
I55AE222D
Cable installaon in compliance with US Naonal Electrical Code NFPA 70 / Canadian Electrical Code C22.1
operaon without mains choke
Fuse
Characteriscs all acc. to UL 248 / Class CC
Max. rated current A 15 15 30 30
Circuit breaker
Characteriscs -
Max. rated current A 15 15 30 30
operaon with mains choke
Fuse
Characteriscs all acc. to UL 248 / Class CC
Max. rated current A 15 15 30 30
Circuit breaker
Characteriscs -
Max. rated current A 15 15 30 30
Earth-leakage circuit breaker
1-phase mains connecon ≥ 30 mA, type A or B
3-phase mains connecon - ≥ 30 mA, type B - ≥ 30 mA, type B
Mains connecon
Inverter I55AE125B
I55AE125D
I55AE137B
I55AE137D
I55AE155B
I55AE155D
I55AE175B
I55AE175D
I55AE211B
I55AE211D
I55AE215B
I55AE215D
I55AE222B
I55AE222D
Connecon X100
Connecon type pluggable screw terminal
Min. cable cross-secon mm² 1
Min. cable cross-secon AWG 18
Max. cable cross-secon mm² 2.5 6
Max. cable cross-secon AWG 12 10
Stripping length mm 8
Stripping length inch 0.32
Tightening torque Nm 0.5 0.7
Tightening torque lb-in 4.4 6.2
Required tool 0.5 x 3.0 0.6 x 3.5
Electrical installaon
Mains connecon
1-phase mains connecon 230/240 V
35