Parameter Name / value range / [default seng] Info
0x2631:015
(P400.15)
Funcon list: Acvate AI2 setpoint
(Funcon list: Setp: AI2)
For further possible sengs, see parameter
0x2631:001 (P400.01). ^ 532
Assignment of a trigger for the "Acvate AI2 setpoint" funcon.
Trigger = TRUE: analog input 2 is used as setpoint source (if the trigger
assigned has the highest setpoint priority).
Trigger = FALSE: no acon / deacvate funcon again.
4Analog input 2 ^ 601
0 Not connected
Example for operang mode
The keypad is set as standard setpoint source.
Switch S1 starts the motor in forward direcon of rotaon. Switch S1 in the inial posion
stops the motor again.
Switch S2 switches the direcon of rotaon.
Switch S3 acvates analog input 1 as setpoint source.
Switch S4 acvates analog input 2 as setpoint source.
If S3 and S4 are operated at the same me, the analog input 1 is acve as set-
point source since the digital input 3 assigned to this funcon has a higher prior-
ity than the digital input 4.
Connecon plan funcon
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
DO1
X3
S1 S2 S3 S4
1k ...10k
R1
R2
0 ... 10 V
Potenometer R1 Frequency setpoint selecon via AI1
Potenometer R2 Frequency setpoint selecon via AI2
Switch S1 Run
Switch S2 Reverse rotaonal direcon
Switch S3 Acvate AI1 setpoint
Switch S4 Acvate AI2 setpoint
Parameter Name Seng for this example
0x2631:001 (P400.01) Enable inverter Constant TRUE [1]
0x2631:002 (P400.02) Run Digital input 1 [11]
0x2631:004 (P400.04) Reset fault Not connected [0]
0x2631:013 (P400.13) Reverse rotaonal direcon Digital input 2 [12]
0x2631:014 (P400.14) Acvate AI1 setpoint Digital input 3 [13]
0x2631:015 (P400.15) Acvate AI2 setpoint Digital input 4 [14]
0x2631:018 (P400.18) Acvate preset (bit 0) Not connected [0]
0x2824 (P200.00) Control selecon Flexible I/O conguraon [0]
0x2838:003 (P203.03) Stop method Standard ramp [1]
0x2860:001 (P201.01) Frequency control: Default setpoint source Keypad [1]
Flexible I/O conguraon
Setpoint change-over
Analog input setpoint source
549

Table of Contents

Other manuals for Lenze i55AE155F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i55AE155F and is the answer not in the manual?

Lenze i55AE155F Specifications

General IconGeneral
BrandLenze
Modeli55AE155F
CategoryInverter
LanguageEnglish

Related product manuals