Restart or stop communicaon
The following parameter can be used to restart or stop communicaon. Oponally it is also
possible to reset all communicaon parameters to the default status.
A restart of communicaon is required aer changes of the interface conguraon (e. g. sta-
on address and baud rate) in order that the changed sengs become eecve.
For restarng communicaon, there are two opons:
1.
Switch inverter o and on again.
2.
Set the selecon = "Restart with current values [1]" in 0x2380 (P508.00).
Parameter Name / value range / [default seng] Info
0x2022:003
(P700.03)
Device commands: Save user data
(Device commands: Save user data)
•
For further possible sengs, see parameter
0x2022:001 (P700.01). ^ 418
1 = save current parameter sengs in the main memory of the memory
module with mains failure protecon.
•
It may take some seconds to execute the task. When the task has
been executed successfully, the value 0 is shown.
•
Do not switch o the supply voltage during the saving process and do
not unplug the memory module from the inverter!
•
When the inverter is switched on, all parameters are automacally
loaded from the main memory of the memory module to the RAM
memory of the inverter.
0 O / ready
0x2381:004
(P510.04)
PROFINET sengs: Staon name
(PROFINET se.: Staon name)
•
From version 02.00
Set staon name
•
The change of this parameter becomes only eecve aer a restart.
0x2382:001
(P511.01)
Acve PROFINET sengs: IP address
(PROFINET diag.: IP address)
•
Read only
•
From version 02.00
Display of the acve IP address.
0x2382:004
(P511.04)
Acve PROFINET sengs: Staon name
(PROFINET diag.: Staon name)
•
Read only
•
From version 02.00
Display of the acve staon name.
0x2388
(P516.00)
PROFINET status
(PROFINET status)
•
Read only
•
From version 02.00
Bit coded display of the current Bus status.
Bit 0 Inialized Aer inialisaon, the network component waits for a communicaon
partner and the system power-up.
Bit 1 Online
Bit 2 Connected
Bit 3 IP address error The IP address is invalid. Valid IP addresses are dened according to RFC
3330.
Bit 4 Hardware fault
Bit 6 Watchdog elapsed PROFINET communicaon is connuously interrupted in the
"Data_Exchange" state, e.g. by cable break or failure of the IO Controller.
•
PROFINET communicaon changes to the "No_Data_Exchange" state.
When the watchdog monitoring me specied by the IO Controller has
elapsed, the response set in 0x2859:001 (P515.01) is triggered in the
inverter.
Bit 7 Protocol error
Bit 8 PROFINET stack ok
Bit 9 PROFINET stack not congured
Bit 10 Ethernet controller fault
Bit 11 UDP stack fault
Conguring the network
PROFINET
Short setup
378