Sengs required for the "parameter change-over" funcon
The easiest way to make the required sengs is via the parameterisaon dialog in the »EASY
Starter«:
1.
Click the buon to rst select the 10 relevant parameters.
2.
Set values for motor M1 ... M4 in the corresponding elds:
In case of a direct seng in the parameters of the "parameter change-over" funcon:
•
The addresses must be set with the following format: 0xiiiiss00 (iiii = index hexadecimal, ss
= subindex hexadecimal). The keypad serves to select the desired parameter from a list.
•
The values for the motors must be set as integer values. The integer value results from the
mulplicaon of the actual seng value by the factor of the respecve parameter. In the ,
the factor for each parameter must be given.
The following table shows the required sengs:
# Address
0x4041:x (PAR 750/x)
Name Value 1
0x4042:x
(PAR 752/x)
Value 2
0x4043:x
(PAR 753/x)
Value 3
0x4044:x
(PAR 754/x)
Value 4
0x4045:x
(PAR 755/x)
hex decimal
1 0x2B000000 721420288 V/f characterisc shape 0 1 0 0
2 0x2B010200 721486336 Base frequency 60 60 60 50
3 0x2D4B0100 759890176 Maximum ulisaon [60 s] 150 120 150 150
4 0x2B120100 722600192 Fixed boost 25 0 40 20
5 0x2C010400 738264064 Rated speed 1745 3450 1750 1450
6 0x2C010500 738264320 Rated frequency 600 600 600 500
7 0x2C010600 738264576 Rated power 75 75 75 150
8 0x2C010700 738264832 Rated voltage 480 480 480 400
9 0x60750000 1618280448 Motor rated current 2200 2100 2200 3500
10 0x60730000 1618149376 Max current 2000 1500 2000 2000
Addional funcons
Parameter change-over
Example: Selecve control of several motors with one inverter
468