EasyManuals Logo
Home>Siemens>Control Unit>SIMATIC

Siemens SIMATIC User Manual

Siemens SIMATIC
648 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #329 background imageLoading...
Page #329 background image
Analog modules
6.5 Analog input module SM 331; AI 8 x 14 Bit High Speed; isochrone; (6ES7331-7HF0x-0AB0)
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
329
6.5 Analog input module SM 331; AI 8 x 14 Bit High Speed; isochrone;
(6ES7331-7HF0x-0AB0)
Order number
6ES7331-7HF00-0AB0 or 6ES7331-7HF01-0AB0
Properties
8 inputs in 4 channel groups
Measurement type programmable for each channel group:
Voltage
Current
Programmable resolution for each group (13 bits + sign)
Any measuring range per channel group
Programmable diagnostics and diagnostic interrupt
Programmable limit value monitoring for 2 channels
Programmable hardware interrupt when limit is exceeded
High-speed update of measured values
Supports isochronous mode
Electrical isolation from the CPU
Electrically isolated from load voltage (not for 2-wire transducers)
Diagnostics
For information on diagnostics messages at the "group diagnostics" parameter, refer to
chapter Diagnostic messages of analog input modules (Page 296).
Hardware interrupts
Hardware interrupts for channel groups 0 and 1 can be programmed in STEP 7. However,
set a hardware interrupt only for the first channel of a channel group, that is, either at
channel 0, or at channel 2

Table of Contents

Other manuals for Siemens SIMATIC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC and is the answer not in the manual?

Siemens SIMATIC Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC
CategoryControl Unit
LanguageEnglish

Related product manuals