Analog modules
6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0)
S7-300 Module data
412 Manual, 06/2017, A5E00105505-AJ
6.11 Analog input module SM 331, AI 6 x TC isolated
(6ES7331-7PE10-0AB0)
Order number
6ES7331-7PE10-0AB0
Properties
The SM 331; AI 6 x TC isolated analog input module has the following properties:
6 inputs in one group
Electrical isolation 250 VAC between channels
Support for user calibration via SIMATIC PDM
Compensation via internal or external cold spot comparison, or via remote access by
means of a separate thermoresistor module.
Measurement type can be set for each channel
Voltage
Temperature
Resolution of 15 bits + sign
Any measuring range for each channel
Programmable diagnostics and diagnostic interrupt
Limit value monitoring can be set for 6 channels
Programmable hardware interrupt when limit is exceeded
Electrically isolated from the CPU
Resolution
The maximum resolution of the measured value (15 bits + sign or 0.1 K) is independent of
the programmed integration time.
Diagnostics
For information on diagnostics messages at the "group diagnostics" parameter, refer to
chapter Diagnostic messages of analog input modules (Page 296).
Hardware interrupts
Hardware interrupts can be set in
STEP 7
for all channels.

Table of Contents

Other manuals for Siemens SIMATIC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC and is the answer not in the manual?

Siemens SIMATIC Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC
CategoryControl Unit
LanguageEnglish

Related product manuals