Analog modules
6.7 Analog input module SM 331; AI 8 x 12 bit;(6ES7331-7KF02-0AB0)
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
353
6.7 Analog input module SM 331; AI 8 x 12 bit;(6ES7331-7KF02-0AB0)
6.7.1 Analog input module SM 331; AI 8 x 12 bit;(6ES7331-7KF02-0AB0)
Order number
6ES7331-7KF02-0AB0
Properties
8 inputs in 4 channel groups
Programmable measurement type at each channel group
Voltage
Current
Resistance
Temperature
Programmable resolution at each channel group (9/12/14 bits + sign)
Any measuring range selection per channel group
Programmable diagnostics and diagnostic interrupt
Programmable limit value monitoring for 2 channels
Programmable hardware interrupt when limit is exceeded
Electrically isolated to CPU and load voltage (not for 2-wire transducers)
Resolution
The resolution of measured values is directly dependent of the selected integration time. In
other words, the longer the integration time for an analog input channel, the higher the
resolution of a measured value.
Diagnostics
For information on diagnostics messages at the "group diagnostics" parameter, refer to
chapter Diagnostic messages of analog input modules
.
Hardware interrupts
Hardware interrupts for channel groups 0 and 1 can be programmed in
STEP 7
. However,
set a hardware interrupt only for the first channel of a channel group, that is, either at
channel 0, or at channel 2

Table of Contents

Other manuals for Siemens SIMATIC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC and is the answer not in the manual?

Siemens SIMATIC Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC
CategoryControl Unit
LanguageEnglish

Related product manuals