4.2.12.3 Equipment Grounding Specications
4.2.12.3.1 General Grounding Specications
Table 4-78 shows the general grounding specications.
Table 4-78 General grounding specications
No.
Description
1 The working ground and protective ground, including the shielded
ground and the lightning-proof ground of the cable distribution frame
should share the same grounding conductor.
2 The cable trays, shells, metal ventilation pipes, metal doors and windows
in the equipment room should be grounded for protection.
3 The metal parts of the equipment which are electrically oating in
normal conditions should be grounded for protection.
4 The ground cable must be connected securely to the protective ground
bar of the equipment room.
5 Do not use other equipment as part of the ground cable or electrical
connection.