Performing opmisaon with keypad
Since there is no access with the keypad to the motor catalogue, rst the motor data must be
set manually with the keypad according to the manufacturer data/motor data sheet. 4Man-
ual seng of the motor data ^ 164
The following ow diagram shows the opmisaon process with the keypad:
Yes
Yes No
No
No
End
d)
Automatic motor calibration
(non-energized)
c)
Automatic motor identification
(energized)
Set manually:
• Motor data (e.g. according to data on
the motor nameplate)
• Motor control type
• Mechanical load and its coupling
to the motor
• Filter time for speed feedback
Lenze motor
connected?
Identification
(energized)
possible?
Engineering tool
available?
Start
c) If the applicaon enables you to energise the system during the opmisaon procedure, carry out an automac idencaon. This proce-
dure results in the best possible parameter sengs.
4Automac motor idencaon (energized) ^ 199
d) If the applicaon does not enable you to energise the system during the opmisaon procedure, carry out an automac calibraon.
4Automac motor calibraon (non-energized) ^ 200
Motor control
Opmisaon of the control loops
195