Parameter Name / value range / [default seng] Info
0x23B9
(P517.00)
Modbus TCP/IP network status
(MBTCP netw stat)
•
Read only
•
From version 04.00
Display of the acve network status.
0 No conguraon
1 Inializaon
2 Connecon me-out
3 Conguraon error
4 Not connected
5 Connecon established
0x23BA:001
(P580.01)
Modbus TCP stascs: Messages received
(MBTCP stascs: Rx messages)
•
Read only
•
From version 04.00
Display of the total number of messages received.
•
This counter counts both valid and invalid messages.
•
Aer the maximum value has been reached, the counter starts again
"0".
0x23BA:002
(P580.02)
Modbus TCP stascs: Valid messages received
(MBTCP stascs: Valid Rx messag.)
•
Read only
•
From version 04.00
Display of the number of valid messages received.
•
Aer the maximum value has been reached, the counter starts again
"0".
0x23BA:003
(P580.03)
Modbus TCP stascs: Messages with excepons
(MBTCP stascs: Mess. w. except)
•
Read only
•
From version 04.00
Display of the number of messages with excepons that have been
received.
•
Aer the maximum value has been reached, the counter starts again
"0".
0x23BA:005
(P580.05)
Modbus TCP stascs: Messages sent
(MBTCP stascs: Tx messages)
•
Read only
•
From version 04.00
Display of the total number of messages sent.
•
Aer the maximum value has been reached, the counter starts again
"0".
0x23BE:001
(P585.01)
Modbus TCP/IP diagnoscs of last Rx/Tx data: Receive
oset
(MBTCP Tx/Rx diag: Rx oset)
0 ... [0] ... 240
•
From version 04.00
For diagnosc purposes, the last received message (max. 16 bytes) is dis-
played in 0x23BE:002 (P585.02). For longer messages, an oset can be
specied here, indicang from which byte of the message the display of
the 16 bytes is to start.
0x23BE:002
(P585.02)
Modbus TCP/IP diagnoscs of last Rx/Tx data: Last Rx
message
(MBTCP Tx/Rx diag: Last Rx message)
•
Read only
•
From version 04.00
Display of the message received last.
0x23BE:003
(P585.03)
Modbus TCP/IP diagnoscs of last Rx/Tx data: Trans-
mit oset
(MBTCP Tx/Rx diag: Tx oset)
0 ... [0] ... 240
•
From version 04.00
For diagnosc purposes, the last sent message (max. 16 bytes) is dis-
played in 0x23BE:004 (P585.04). For longer messages, an oset can be
specied here, indicang from which byte of the message the display of
the 16 bytes is to start.
0x23BE:004
(P585.04)
Modbus TCP/IP diagnoscs of last Rx/Tx data: Last Tx
message
(MBTCP Tx/Rx diag: Last Tx message)
•
Read only
•
From version 04.00
Display of the message sent last.
0x23B1:005
(P510.05)
Modbus -TCP/IP sengs: IP conguraon
(MBTCP sengs: IP conguraon)
•
From version 04.00
Set IP conguraon.
0 Stored IP The currently saved IP conguraon is used.
1 BOOTP The IP conguraon is assigned by the master via BOOTP.
2 DHCP The IP conguraon is assigned by the Master via DHCP.
The assignment of a gateway address that is not in the same subnetwork
as the IP address, is denied.
Conguring the network
Modbus TCP
Diagnoscs