Parameter Name / value range / [default seng] Info
0x2911:001
(P450.01)
Frequency setpoint presets: Preset 1
(Freq. presets: Freq. preset 1)
0.0 ... [20.0] ... 599.0 Hz
Parameterisable frequency setpoints (presets) for operang mode "MS:
Velocity mode".
0x2911:002
(P450.02)
Frequency setpoint presets: Preset 2
(Freq. presets: Freq. preset 2)
0.0 ... [40.0] ... 599.0 Hz
0x2911:003
(P450.03)
Frequency setpoint presets: Preset 3
(Freq. presets: Freq. preset 3)
Device for 50-Hz mains: 0.0 ... [50.0] ... 599.0 Hz
Device for 60-Hz mains: 0.0 ... [60.0] ... 599.0 Hz
0x2915
(P210.00)
Minimum frequency
(Min. frequency)
0.0 ... [0.0] ... 599.0 Hz
Lower limit value for all frequency setpoints.
0x2916
(P211.00)
Maximum frequency
(Max. frequency)
Device for 50-Hz mains: 0.0 ... [50.0] ... 599.0 Hz
Device for 60-Hz mains: 0.0 ... [60.0] ... 599.0 Hz
Upper limit value for all frequency setpoints.
0x2917
(P220.00)
Acceleraon me 1
(Accelerat.me 1)
0.0 ... [5.0] ... 3600.0 s
Acceleraon me 1 for the operang mode "MS: Velocity mode".
•
The acceleraon me set refers to the acceleraon from standsll to
the maximum frequency set. In the case of a lower setpoint selecon,
the actual acceleraon me is reduced accordingly.
•
Seng is not eecve in the operang mode 0x6060 (P301.00) =
"CiA: Velocity mode [2]". 4Device prole CiA 402 ^ 469
0x2918
(P221.00)
Deceleraon me 1
(Decelerat.me 1)
0.0 ... [5.0] ... 3600.0 s
Deceleraon me 1 for the operang mode "MS: Velocity mode".
•
The deceleraon me set refers to the deceleraon from the maxi-
mum frequency set to standsll. In the case of a lower actual fre-
quency, the actual deceleraon me is reduced accordingly.
•
Seng is not eecve in the operang mode 0x6060 (P301.00) =
"CiA: Velocity mode [2]". 4Device prole CiA 402 ^ 469
0x291C
(P225.00)
Quick stop deceleraon me
(QSP dec. me)
0.0 ... [1.0] ... 3600.0 s
Quick stop deceleraon me for the operang mode "MS: Velocity
mode".
•
If the "Quick stop" funcon is acvated, the motor is brought to a
standsll within the deceleraon me set here.
•
The deceleraon me set refers to the deceleraon from the maxi-
mum frequency set to standsll. In the case of a lower actual fre-
quency, the actual deceleraon me is reduced accordingly.
•
Seng is not eecve in the operang mode 0x6060 (P301.00) =
"CiA: Velocity mode [2]". 4Device prole CiA 402 ^ 469
All possible basic sengs are described in the "Basic seng" chapter. ^ 143
Commissioning
Parameter seng
Basic inverter sengs
80