4 Parameter List
4 - 40
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Parameter
No.
Function name
Monitor or data range
Default
data
Set
data
Changes
during
RUN
Unit
Page
Modbus
mapping
P200
Modbus Mapping
Function Selection
00: Standard Mod-
bus address
01: Modbus mapping
enabled
00
Enabled
−
P. 8-25
P201
Modbus Mapping Exter-
nal Register 1 to 10
0000 to FFFF hex
0000
Enabled
−
P. 8-25
P202
P203
P204
P205
P206
P207
P208
P209
P210
P211
Modbus Mapping Exter-
nal Register Type 1 to
10
00: Unsigned
01: Signed
00
Enabled
−
P. 8-25
P212
P213
P214
P215
P216
P217
P218
P219
P220
P221
Modbus Mapping Scal-
ing 1 to 10
0.001 to 65.535
1.000
Enabled
−
P. 8-25
P222
P223
P224
P225
P226
P227
P228
P229
P230
P301
Modbus Mapping Internal
Register 1 to 10
0000 to FFFF hex
0000
Enabled
−
P. 8-25
P302
P303
P304
P305
P306
P307
P308
P309
P310
P400
Modbus Mapping Endian
Selection
00: Big endian
01: Little endian
02: Special endian
00
Enabled
−
P. 8-29