Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
7-5-2 Reduced Voltage Startup Selection
Use this function to increase the voltage slowly during motor startup.
To prevent the surge current or overcurrent trip during startup, increase the value set in the Reduced
Voltage Startup Selection (b036). Although setting a small value causes the high starting torque, the
inverter operates as with the full voltage starting. Therefore, an overcurrent trip may occur easily.
Reduced Voltage
Startup Selection
0: Reduced voltage startup disabled
1 (Reduced voltage startup time: short) to
255 (Reduced voltage startup time: long)
7-5-3 Frequency Jump Function
Use the frequency jump function to avoid the resonant point of the load machine during operation.
If jump frequency is set, you cannot set the frequency reference within the jump frequency range to
avoid steady operation in that range.
The output frequency changes continuously according to the acceleration/deceleration time settings
during acceleration/deceleration.
You can set three points for jump frequency.
0.00 to 590.00
Set the center of the jump frequency.
*1
Jump Frequency Width
1/2/3
0.00 to 10.00 (100.00)
*2
Set 1/2 of the jump frequency width.
*1. When set to 0 Hz, this function is disabled.
*2. In high-frequency mode.