Detailed Description
2.12 Block descriptions
PLC Basic Program Solution Line (P3 sl)
Function Manual, 08/2005 Edition, 6FC5397-0BP10-0BA0
2-143
// Save override
L DB21.DBB 4; //Feed override interface
T EB 28; //Buffer storage (freely assign. input or memory byte)
wei1:
U M 100.2; //Switchover takes place
O DB10.DBX 104.0; //MCP1Ready
JCN smth2;
U DB10.DBX 104.0; //MCP1Ready
FP M 100.1; //Edge trigger flag 2
JC smth2;
U M 100.2; //Switchover takes place
R M 100.2; //Reset auxiliary flag 1
JC smth2;
U M 100.3; //Comparison has taken place
SPB MCP; //Call MCP program
// Route the stored override to the interface of the switched MCP
// until the override values match
L EB28; //Buffer storage open
T DB21.DBB 4; //Route override interface
L EB 3; //Override input byte for feed
<>i; //Match?
JC smth2; //No, jump
S M100.3; //Yes, set auxiliary flag 2
// When override values match, call the MCP program again
MCP: CALL "MCP_IFM"( //FC 19
BAGNo := B#16#1,
ChanNo := B#16#1,
SpindleIFNo := B#16#0,
FeedHold := M 101.0,
SpindleHold := M 101.1);
wei2: NOP 0;
2.12.8 FB 10: Safety relay (SI relay)
Description of functions
The SPL block "Safety relay" for "Safety Integrated" is the PLC equivalent of the NC function
of the same name. The standard SPL "Safety relay" block is designed to support the
implementation of an emergency stop function with safe programmable logic. However, it
can also be used to implement other similar safety functions, e.g., control of a protective
door.