Unidrive M702 User Guide 229
Issue Number: 3
Table 12-2 Maximum permissible continuous output current @ 40 °C (104 °F) ambient with high IP insert installed
Model
Normal Duty
Heavy Duty
Maximum permissible continuous output current (A)
for the following switching frequencies
Maximum permissible continuous output current (A)
for the following switching frequencies
2
kHz
3
kHz
4
kHz
6
kHz
8
kHz
12
kHz
16
kHz
2
kHz
3
kHz
4
kHz
6
kHz
8
kHz
12
kHz
16
kHz
200 V
03200050 6.6 5.0
03200066 8.0 6.6
03200080 11.0 9.7 8.0 6.9
03200106 12.7 11.0 9.7 10.6 10.4 9.3 8.0 6.9
04200137 18.0 16.3 14.2 13.1 13.7 13.2
04200185 24.7 22.5 20.7 18.2 16.5 14.2 13.2 18.5 18.1 16.2 14.2 13.1
05200250 17.1 15.6 14.4 12.6 11.4 9.6 8.7 17.0 15.7 14.5 12.7 11.5 9.8 9.8
400 V
03400025 3.4 3.3 2.5
03400031 4.5 4.4 4.1 3.6 3.3 3.1
03400045 5.1 4.9 4.7 4.4 4.1 3.6 3.3 4.5 4.4 4.1 3.6 3.2
03400062 7.7 6.2 5.2 6.2 5.6 4.5 3.8
03400078 10.4 9.9 9.0 6.4 4.8 7.8 6.6 4.8 3.6
03400100 12.3 11.9 11.1 10.0 9.0 6.4 4.8 10.0 9.4 7.8 6.6 4.8 3.6
04400150 8.9 8.7 8.3 7.0 8.7 8.4 7.0
04400172 8.6 8.4 6.9 8.7 8.4 7.0
05400270 17.1 15.6 14.4 12.6 11.4 9.6 8.7 17.2 15.6 14.5 12.6 11.3 9.7 8.6
05400300 19.8 19.5 18.9 17.6 16.4 13.9 11.7 19.8 19.5 18.9 17.7 16.2 13.8 11.7
575 V
05500030 3.9 3.0
05500040 6.1 4.0
05500069 10.0 6.9