Unidrive M702 User Guide 273
Issue Number: 3
User Program On board user program error
249
The User Program trip indicates that an error has been detected in the onboard user program image. The reason for the trip
can be identified by the sub-trip number.
Trip Diagnosis
Sub-trip Reason Comments
1 Divide by zero
2 Undefined trip
3
Attempted fast parameter access set-up with
non-existent parameter
4 Attempted access to non-existent parameter
5 Attempted write to read-only parameter
6 Attempted and over-range write
7 Attempted read from write-only parameter
30
The image has failed because either its CRC
is incorrect, or there are less than 6 bytes in
Occurs when the drive powers-up or the image is
programmed. The image tasks will not run
31
The image requires more RAM for heap and
stack than can be provided by the drive.
As 30
32
The image requires an OS function call that is
higher than the maximum allowed
As 30
33 The ID code within the image is not valid As 30
34
The derivative image has been changed for
an image with a different derivative number.
As 30
40
The timed task has not completed in time and
has been suspended
41
Undefined function called, i.e. a function in the
host system vector table that has not been
As 40
51
Core menu customization table CRC check
failed
As 30
52 Customized menu table CRC check failed As 30
53 Customized menu table changed
Occurs when the drive powers-up or the image is
programmed and the table has changed. Defaults are
61
The option module installed in slot 1 is not
allowed with the derivative image
As 30
62
The option module installed in slot 2 is not
allowed with the derivative image
As 30
63
The option module installed in slot 3 is not
allowed with the derivative image
As 30
64
The option module installed in slot 4 is not
allowed with the derivative image
As 30
70
An option module that is required by the
derivative image is not installed in any slot.
As 30
71
An option module specifically required to be
installed in slot 1 not present
As 30
72
An option module specifically required to be
installed in slot 2 not present
As 30
73
An option module specifically required to be
installed in slot 3 not present
As 30
74
An option module specifically required to be
installed in slot 4 not present
As 30
80 Image is not compatible with the control board Initiated from within the image code
81
Image is not compatible with the control board
serial number
As 80

Table of Contents

Other manuals for Emerson Unidrive M702

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Unidrive M702 and is the answer not in the manual?

Emerson Unidrive M702 Specifications

General IconGeneral
BrandEmerson
ModelUnidrive M702
CategoryController
LanguageEnglish

Related product manuals