GE Multilin T60 Transformer Protection System 5-11
5 SETTINGS 5.2 PRODUCT SETUP
5
PASSWORD LOCKOUT DURATION: This setting specifies the time that the T60 will lockout password access after
the number of invalid password entries specified by the INVALID ATTEMPTS BEFORE LOCKOUT setting has occurred.
The T60 provides a means to raise an alarm upon failed password entry. Should password verification fail while accessing
a password-protected level of the relay (either settings or commands), the UNAUTHORIZED ACCESS FlexLogic operand is
asserted. The operand can be programmed to raise an alarm via contact outputs or communications. This feature can be
used to protect against both unauthorized and accidental access attempts.
The
UNAUTHORIZED ACCESS operand is reset with the COMMANDS  CLEAR RECORDS  RESET UNAUTHORIZED
ALARMS command. Therefore, to apply this feature with security, the command level should be password-protected. The
operand does not generate events or targets.
If events or targets are required, the UNAUTHORIZED ACCESS operand can be assigned to a digital element programmed
with event logs or targets enabled.
The access level timeout settings are shown below.
PATH: SETTINGS PRODUCT SETUP SECURITY  ACCESS SUPERVISION ACCESS LEVEL TIMEOUTS
These settings allow the user to specify the length of inactivity required before returning to the restricted access level. Note
that the access level will set as restricted if control power is cycled.
COMMAND LEVEL ACCESS TIMEOUT: This setting specifies the length of inactivity (no local or remote access)
required to return to restricted access from the command password level.
SETTING LEVEL ACCESS TIMEOUT: This setting specifies the length of inactivity (no local or remote access)
required to return to restricted access from the command password level.
DUAL PERMISSION SECURITY ACCESS
PATH: SETTINGS PRODUCT SETUP SECURITY  DUAL PERMISSION SECURITY ACCESS
The dual permission security access feature provides a mechanism for customers to prevent unauthorized or unintended
upload of settings to a relay through the local or remote interfaces interface.
The following settings are available through the local (front panel) interface only.
LOCAL SETTING AUTH: This setting is used for local (front panel or RS232 interface) setting access supervision.
Valid values for the FlexLogic operands are either “On” (default) or any physical “Contact Input ~~ On” value.
If this setting is “On“, then local setting access functions as normal; that is, a local setting password is required. If this
setting is any contact input on FlexLogic operand, then the operand must be asserted (set as on) prior to providing the
local setting password to gain setting access.
If setting access is not authorized for local operation (front panel or RS232 interface) and the user attempts to obtain
setting access, then the
UNAUTHORIZED ACCESS message is displayed on the front panel.
If this setting is "Off," firmware upgrades are blocked. If this setting is "On," firmware upgrades are allowed.
REMOTE SETTING AUTH: This setting is used for remote (Ethernet or RS485 interfaces) setting access supervision.
ACCESS LEVEL
TIMEOUTS
COMMAND LEVEL ACCESS
TIMEOUT: 5 min
Range: 5 to 480 minutes in steps of 1
MESSAGE
SETTING LEVEL ACCESS
TIMEOUT: 30 min
Range: 5 to 480 minutes in steps of 1
DUAL PERMISSION
SECURITY ACCESS
LOCAL SETTING AUTH:
On
Range: selected FlexLogic operands (see below)
MESSAGE
REMOTE SETTING AUTH:
On
Range: FlexLogic operand
MESSAGE
ACCESS AUTH
TIMEOUT: 30 min.
Range: 5 to 480 minutes in steps of 1