GE Multilin T60 Transformer Protection System 5-213
5 SETTINGS 5.6 GROUPED ELEMENTS
5
5.6.6 TRANSFORMER ELEMENTS
a) MAIN MENU
PATH: SETTINGS  GROUPED ELEMENTS SETTING GROUP 1(6) TRANSFORMER
This menu contains the settings for the transformer differential elements and the transformer thermal elements.
The thermal elements include hottest-spot temperature, aging factor and loss of life. The computation of these elements fol-
lows IEEE standards C57.91-1995: “IEEE Guide for Loading Mineral-Oil-Immersed Transformers” and C57.96-1989: “IEEE
Guide for Loading Dry-Type Distribution Transformers”. The computations are based on transformer loading conditions,
ambient temperature, and the entered transformer data.
TRANSFORMER
PERCENT
DIFFERENTIAL
See page 5–214.
MESSAGE
INSTANTANEOUS
DIFFERENTIAL
See page 5–219.
MESSAGE
HOTTEST-SPOT
TEMPERATURE
See page 5–219.
MESSAGE
AGING FACTOR
See page 5–220.
MESSAGE
LOSS OF LIFE
See page 5–221.