EasyManuals Logo
Home>GE>Relays>T60

GE T60 User Manual

GE T60
770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #522 background imageLoading...
Page #522 background image
8-2 T60 Transformer Protection System GE Multilin
8.1 DIFFERENTIAL CHARACTERISTIC TEST 8 COMMISSIONING
8
c) SLOPE 1 / BREAKPOINT 1
The point of Slope 1 and Breakpoint 1 is tested as follows. Refer to the Differential Restraint Characteristic diagram below
for details.
1. Inject current (I
y
) into Winding 2 Phase A as follows:
(EQ 8.2)
2. At Breakpoint 1, the injected current I
XOP1
is determined by:
(EQ 8.3)
and the differential current should be equal to:
(EQ 8.4)
3. Preset the I
x
current to . Switch on the test set. The relay should restraint, as the differential to restraint
ratio will become less than the Slope 1 setting. Switch off the current.
4. Preset the I
x
current to . Switch on the test set. The relay should operate. Switch off the current.
To test any other point from the Slope 1 section of the curve, inject a per-unit restraint current smaller than the Breakpoint 1
current and repeat the steps above by substituting the Breakpoint 1 value with the new per-unit restraint current value into
the equations above.
d) SLOPE 2 / BREAKPOINT 2
The point of Slope 2 and Breakpoint 2 is tested as follows. Refer to the diagram below for details.
1. Preset the I
y
current to a magnitude that results in the restraint current being equal to Breakpoint 2. Use the following
calculation to define the magnitude of the injected current:
(EQ 8.5)
2. At the above current (restraint), the I
XOP2
current required to operate the element is calculated as:
(EQ 8.6)
3. Preset the I
x
current to and switch on the test set. The relay should restrain, as the differential to restraint
ratio will become less than the Slope 2 setting. Switch off the current.
4. Preset the I
x
current to . Switch on the test set and verify relay operation. Switch off the current.
To test any point from the Slope 2 portion of the characteristic, inject a per-unit restraint current greater than the Breakpoint
2 current as restraint and repeat the steps above by substituting the Breakpoint 2 value in the equations above with the new
per-unit restraint current value.
The above two tests can be repeated for Phases B and C.
Figure 8–1: DIFFERENTIAL RESTRAINT CHARACTERISTIC
I
YB1
Breakpoint 1
CT
M[2]
-----------
=
I
XOP1
Breakpoint 1 1 Slope 1
CT
M[1]
-----------
=
I
d
Slope 1 (in %) Breakpoint 1 (in pu)=
1.05 I
XOP1
0.95 I
XOP1
I
YB2
Breakpoint 2
CT
M[2]
-----------
=
I
XOP2
Breakpoint 2 1 Slope 2
CT
M[1]
-----------
=
1.05 I
XOP1
0.95 I
XOP1
I
d
(pu)
I
r
(pu)
PKP
B
1
S
2
S
1
B
2

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE T60 and is the answer not in the manual?

GE T60 Specifications

General IconGeneral
BrandGE
ModelT60
CategoryRelays
LanguageEnglish

Related product manuals