Automac start aer switching on the mains voltage
The automac start can be acvated in 0x2838:002 (P203.02).
Precondions for the automac start:
Flexible I/O conguraon is selected: 0x2824 (P200.00) = "Flexible I/O conguraon [0]"
For the start command, a digital input has been congured. (In case of keypad or acvated
network control, an automac start is not possible.)
The following diagram demonstrates the funcon:
t
0 Hz
30 Hz
10 Hz
20 Hz
40 Hz
50 Hz
60 Hz
0 Hz
30 Hz
10 Hz
20 Hz
40 Hz
50 Hz
60 Hz
t
t
t
0 Hz
30 Hz
10 Hz
20 Hz
40 Hz
50 Hz
60 Hz
t
t
0x2838 002:
0x2838 002:
0x2DDD
Mains voltage
= On [1]
= Off [0]
Digital input 1 [11] Run
Constant TRUE [1]
Output signals
Output frequency
Enable inverter
Input signals
Frequency setpoint selection
FunctionTrigger
Start at power-up = "O [0]": Aer switching on the mains voltage, a renewed start command is required to start the motor.
Start at power-up = "On [1]": Aer switching on the mains voltage, the motor starts automacally if a start command is acve.
Parameter Name / value range / [default seng] Info
0x2838:001
(P203.01)
Start/stop conguraon: Start method
(Start/stop confg: Start method)
Seng can only be changed if the inverter is inhibi-
ted.
Behaviour aer start command.
0 Normal Aer start command, the standard ramps are acve.
Acceleraon me 1 can be set in 0x2917 (P220.00).
Deceleraon me 1 can be set in 0x2918 (P221.00).
1 DC braking Aer start command, the "DC braking" funcon is acve for the me set
in 0x2B84:002 (P704.02).
4DC braking ^ 437
2 Flying restart circuit Aer the start command, the ying restart circuit is acve.
The ying restart funcon makes it possible to restart a coasng motor
during operaon without speed feedback. Synchronicity between the
inverter and motor is coordinated so that the transion to the rotang
motor is eected without jerk at the me of connecon.
4Flying restart circuit ^ 481
3 Start with magnesaon
0x2838:002
(P203.02)
Start/stop conguraon: Start at power-up
(Start/stop confg: Start at powerup)
Starng performance aer switching on the mains voltage.
0 O No automac start aer switching on mains voltage. In addion to the
inverter enable, a renewed start command is always required to start the
motor.
1 On Automac start of the motor aer switching on the mains voltage if the
inverter is enabled and a start command exists.
Basic seng
Starng/stopping performance
Starng performance
154

Table of Contents