EasyManuals Logo

Lenze i55AE155F User Manual

Lenze i55AE155F
702 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #361 background imageLoading...
Page #361 background image
Predened Modbus status registers
These registers are only provided with read access.
The cross-reference in column 2 leads to the detailed parameter descripon.
Modbus registers Permanently assigned parameter
Address Name
42001 0x400C:001 (P593.01) AC Drive status word
42002 0x400C:006 (P593.06) Frequency (0.01)
42003 0x603F (P150.00) Error code
42004 0x400C:005 (P593.05) Drive status
42005 0x2D89 (P106.00) Motor voltage
42006 0x2D88 (P104.00) Motor current
42007 0x6078 (P103.00) Current actual value
42008 0x2DA2:002 (P108.02) Apparent power
(42008 = High Word, 42009 = Low Word)
42009
42010 0x2D84:001 (P117.01) Heatsink temperature
42011 0x2D87 (P105.00) DC-bus voltage
42012 0x60FD (P118.00) Digital inputs (only bit 16 ... bit 31)
42013 0x6077 (P107.00) Torque actual value
42014 ... 42021 - Reserved
Variable mapping
Via 0x23BB:001 ... 0x23BB:024 (P530.01 ... 24), 24 registers can be mapped to parameters
of the inverter.
Format: 0xiiiiss00 (iiii = index, ss = subindex)
The display of the internal Modbus register numbers in 0x23BC:001 ... 0x23BC:024
(P531.01 ... 24) is generated automacally. Since 32-bit parameters require two registers,
there is no 1:1 assignment.
For the mappable registers, a CRC (Cyclic Redundancy Check) is executed. The checksum
determined is displayed in 0x23BD (P532.00). The user can read this "validaon code" and
use it for comparison in the Modbus master. In this way it can be checked whether the
inverter currently queried is congured correctly for the respecve applicaon.
Parameter Name / value range / [default seng] Info
0x23BB:001 ...
0x23BB:024
(P530.01 ... 24)
Modbus TCP/IP parameter mapping: Parameter 1 ...
Parameter 24
(MBTCP param.mapp: Parameter 1 ... Parameter 24)
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
Mapping entries for Modbus register 40103 ... 40149.
Format: 0xiiiiss00 (iiii = index, ss = subindex)
0x23BC:001 ...
0x23BC:024
(P531.01 ... 24)
Register assignment: Register 1 ... Register 24
(Register assignm: Register 1 ... Register 24)
Read only
Display of the internal Modbus register number starng from which the
parameter mapped in 0x23BB:001 ... 0x23BB:024 (P530.01 ... 24) is
stored.
For the rst parameter mapped, always 2500.
From the second parameter mapped, 2500 + oset. The oset results
from the data types of the previously mapped parameters.
0x23BD
(P532.00)
Vericaon code
(Vericat. code)
Read only
From version 04.00
Conguring the network
Modbus TCP
Data mapping
361

Table of Contents

Other manuals for Lenze i55AE155F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i55AE155F and is the answer not in the manual?

Lenze i55AE155F Specifications

General IconGeneral
BrandLenze
Modeli55AE155F
CategoryInverter
LanguageEnglish

Related product manuals