Parameter Name / value range / [default seng] Info
0x2631:008
(P400.08)
Funcon list: Run forward (CW)
(Funcon list: Run forward)
•
Seng can only be changed if the inverter is inhibi-
ted.
•
For further possible sengs, see parameter
0x2631:001 (P400.01). ^ 532
Assignment of a trigger for the "Run forward (CW)" funcon.
Trigger = TRUE: Let motor rotate forward.
Trigger = FALSE: Stop motor.
Notes:
•
In order to start the motor, "Enable inverter" 0x2631:001 (P400.01)
and "Run" 0x2631:002 (P400.02) must be set to TRUE.
•
The inverter always responds to the run command detected last (if
start enable is available).
•
The stop method can be selected in 0x2838:003 (P203.03).
• In the case of a bipolar setpoint selecon (e.g ±10 V), the funcon is
executed irrespecve of the rotang direcon. The rotang direcon
is determined by the sign of the setpoint.
•
The "Run forward (CW)" funcon also serves to realise an automac
start aer switch-on. 4Starng performance ^ 153
0 Not connected
0x2631:009
(P400.09)
Funcon list: Run reverse (CCW)
(Funcon list: Run reverse)
•
Seng can only be changed if the inverter is inhibi-
ted.
•
For further possible sengs, see parameter
0x2631:001 (P400.01). ^ 532
Assignment of a trigger for the "Run reverse (CCW)" funcon.
Trigger = TRUE: Let motor rotate backward.
Trigger = FALSE: Stop motor.
Notes:
•
In order to start the motor, "Enable inverter" 0x2631:001 (P400.01)
and "Run" 0x2631:002 (P400.02) must be set to TRUE.
•
The inverter always responds to the run command detected last (if
start enable is available).
•
The stop method can be selected in 0x2838:003 (P203.03).
• In the case of a bipolar setpoint selecon (e.g ±10 V), the funcon is
executed irrespecve of the rotang direcon. The rotang direcon
is determined by the sign of the setpoint.
•
The "Run reverse (CCW)" funcon also serves to realise an automac
start aer switch-on. 4Starng performance ^ 153
0 Not connected
0x2631:010
(P400.10)
Funcon list: Jog foward (CW)
(Funcon list: Jog foward)
•
Seng can only be changed if the inverter is inhibi-
ted.
•
For further possible sengs, see parameter
0x2631:001 (P400.01). ^ 532
Assignment of a trigger for the "Jog foward (CW)" funcon.
Trigger = TRUE: Let motor rotate forward with preset 5.
Trigger = FALSE: Stop motor.
CAUTION!
The jog operaon has a higher priority than the "Run" funcon, all other
start commands and the keypad key .
•
If jog operaon is acve, the motor cannot be stopped with the previ-
ously menoned funcons!
•
However, jog operaon can be interrupted by the "Quick stop" func-
on.
Notes:
•
The preset value 5 can be set in 0x2911:005 (P450.05).
•
The stop method can be selected in 0x2838:003 (P203.03).
•
If "Jog foward (CW)" and "Jog reverse (CCW)" are acvated at the
same me, the motor is stopped using the stop method and jog oper-
aon must be triggered again.
•
Jog operaon cannot be started automacally. The "Start at power-
up" opon in 0x2838:002 (P203.02) does not apply to jog operaon.
0 Not connected
Flexible I/O conguraon
Start / stop motor
535