Component replacement (software/hardware)
9
9.1 Safety instructions
WARNING
Unsafe operating state after POWER ON
After a firmware update, the system generally requests a POWER ON. After a POWER ON,
an unsafe operating state can occur - and if persons are in the hazardous area, this can result
in death or severe injury.
After each POWER ON, perform an acceptance test and create an acceptance report.
Do not enter the danger zone of the motor until the acceptance test has been successfully
completed.
WARNING
Unwanted motion if components are replaced without a function test
After a component replacement, connections or functions can be defective so that death or
serious injury can result if a person enters the danger zone of the motors.
Perform a POWER ON before resuming operation.
After component replacement, always run a simplified function test.
More detailed information can be found in Chapter "Acceptance test in the SINUMERIK
ONE Commissioning Tool (Page 341)".
Safety Integrated (with SINAMICS S120)
Commissioning Manual, 02/2020, A5E46305916B AB 343

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINUMERIK MC and is the answer not in the manual?

Siemens SINUMERIK MC Specifications

General IconGeneral
BrandSiemens
ModelSINUMERIK MC
CategoryControl Systems
LanguageEnglish

Related product manuals