1.4 Scope of Functions
The numerical Distance Protection SIPROTEC
®
7SA6 has the following functions
(sometimes dependent on the order variant):
Distance Protection Protection for all types of short-circuit in systems with earthed, resonant-earthed or
isolated star point;
Different pickup schemes enable the user to adapt the distance protection system
to different network conditions and user’s requirements:
overcurrent pickup, voltage and angular-controlled pickup or impedance starting
(with polygonal angle-dependent characteristeric) can be selected;
Reliable distinction between load and short-circuit conditions, also on long, heavily
loaded lines;
High sensitivity in the case of a weakly loaded system, extreme stability against
load jumps and power swings;
Optimum adaption to line conditions by means of a polygonal tripping characteristic
with separate setting along the X–axis (reach) and R–axis (arc resistance reserve),
separate R–setting for earth faults.
Six measuring systems for each distance zone (full scheme design);
Six distance zones, selectable as forward, reverse or non-directional reaching, one
may be graded as an overreaching zone;
Nine time stages for the distance zones;
Direction determination is done with unfaulted loop (quadrature) voltages and
voltage memory, thereby achieving unlimited directional sensitivity, and not
affected by capacitive voltage transformer transients;
Current transformer saturation detection and compensation;
Compensation against the influence of a parallel line;
Shortest tripping time is approx. 15 ms (f
N
=60Hz)or17ms(f
N
=50Hz);
Phase segregated tripping (in conjunction with single-pole or single- and three-pole
auto-reclosure);
Non-delayed tripping after switching on to a fault;
Two sets of zero sequence compensation factors.
Power Swing
Suppplement
(optional
for Impedance
Starting)
Power swing detection with dZ/dt–measurement with three measuring systems;
Power swing detection up to a maximum of 7 Hz swing frequency;
In service also during single-pole dead times ;
Settable power swing programs;
Prevention of undesired tripping by the distance protection during power swings;
Tripping for out-of-step conditions can also be configured.
Teleprotection
Supplement
Can be configured to various schemes for:
Permissive Underreach Transfer Trip (PUTT) (directly via pickup or via overreach
zone that is set separately)

Table of Contents

Other manuals for Siemens siprotec 7SA6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA6 and is the answer not in the manual?

Siemens siprotec 7SA6 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA6
CategoryRelays
LanguageEnglish

Related product manuals