Functions
6-3137SA6 Manual
C53000-G1176-C156-2
but also consumes storage capacity during the auto-reclosure dead time(s). This set-
tingcanonlybemodifiedwithDIGSI
®
4 under Additional Settings”.
The actual storage time encompasses the pre-fault time
PRE. TRIG. TIME (address
411) ahead of the reference instant, the normal recording time and the post-fault time
POST REC. TIME (address 412) after the storage criterion has reset. The maximum
permissible storage period per fault recording
MAX. LENGTH is set in address 410.
The fault recording can also be triggered via a binary input, via the keypad on the front
of the device or with a PC via the operation or service interface. The storage is then
dynamically triggered. The length of the fault recording is set in address
415 BinIn
CAPT.TIME
(maximum length however is MAX. LENGTH,address 410). The pre-
and post-fault times are additive. If the time for the binary input is set to
, the duration
of the storage is as long as the binary input is initiated (static), the maximum length
however still is
MAX. LENGTH (address 410).
6.23.5 Settings
Addresses which have an „A“ attached to its end can only be changed with DIGSI
®
4
in
Additional Settings
Average
Calculation
Min/Max Values
Addr. Setting Title Setting Options Default Setting Comments
2801 DMD Interval 15 Min per., 1 Sub
15 Min per., 3 Subs
15 Min per., 15 Subs
30 Min per., 1 Sub.
60 Min per., 1 Sub.
60 Min per., 1 Sub. Demand Calculation Intervals
2802 DMD Sync.Time On the Hour
15 Min. after Hour
30 Min. after Hour
45 Min. after Hour
On the Hour Demand Synchronization Time
Addr. Setting Title Setting Options Default Setting Comments
2811 MinMax cycRESET NO
YES
YES Automatic Cyclic Reset Function
2812 MiMa RESET TIME 0..1439 min 0 min MinMax Reset Timer
2813 MiMa RESET-
CYCLE
1..365 day(s) 7 day(s) MinMax Reset Cycle Period
2814 MinMax-
RES.START
1..365 Days 1 Days MinMax Start Reset Cycle in

Table of Contents

Other manuals for Siemens siprotec 7SA6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA6 and is the answer not in the manual?

Siemens siprotec 7SA6 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA6
CategoryRelays
LanguageEnglish

Related product manuals