Technical Data
10-437SA6 Manual
C53000-G1176-C156
10.20 Transmission of Binary Information (optional)
Note: The setting for “remote signal reset delay for communication failure” may be 0 s
to 300 s or
∞. With setting ∞ annunciations are maintained permanently.
RemoteCommands Number of possible remote commands 4
Operating times, total approx.
Drop-off times, total approx.
The operating times refer to the output of commands via accelerated output relays. For high-
speed relays (7SA6*1*–*M/N/P, 7SA6*2*–*M/N/P/Q/R/S) approx. 5 ms can be subtracted from
the time values.
Remote
Annunciations
Number of possible remote annunciations 24
Operating times, total approx.
Drop-off times, total approx.
The operating times refer to the output of commands via accelerated output relays.
transmission speed 512 kbit/s 128 kbit/s 64 kbit/s
2 ends, minimum,
typical
12 ms
14 ms
14 ms
16 ms
16 ms
18 ms
3 ends, minimum,
typical
13 ms
15 ms
16 ms
19 ms
21 ms
24 ms
transmission speed 512 kbit/s 128 kbit/s 64 kbit/s
2 ends, minimum,
typical
10 ms
12 ms
12 ms
14 ms
13 ms
16 ms
3 ends, minimum,
typical
10 ms
12 ms
13 ms
16 ms
18 ms
21 ms
transmission speed 512 kbit/s 128 kbit/s 64 kbit/s
2 ends, minimum,
typical
12 ms
14 ms
14 ms
16 ms
16 ms
18 ms
3 ends, minimum,
typical
13 ms
15 ms
16 ms
19 ms
21 ms
24 ms
transmission speed 512 kbit/s 128 kbit/s 64 kbit/s
2 ends, minimum,
typical
10 ms
12 ms
13 ms
14 ms
13 ms
16 ms
3 ends, minimum,
typical
10 ms
12 ms
13 ms
16 ms
18 ms
21 ms