Functions
6-314 7SA6 Manual
C53000-G1176-C156-2
Waveform Capture
6.23.6 Information Overview
Average
Calculation
Min/Max Values
Addr. Setting Title Setting Options Default Setting Comments
402A WAVEFORMTRIG-
GER
Save with Pickup
Save with TRIP
Start with TRIP
Save with Pickup Waveform Capture
403A WAVEFORM DATA Fault event
Power System fault
Fault event Scope of Waveform Data
410 MAX. LENGTH 0.30..5.00 sec 2.00 sec Max. length of a Waveform Cap-
ture Record
411 PRE. TRIG. TIME 0.05..0.50 sec 0.25 sec Captured Waveform Prior to
Trigger
412 POST REC. TIME 0.05..0.50 sec 0.10 sec Captured Waveform after Event
415 BinIn CAPT.TIME 0.10..5.00 sec; ∞ 0.50 sec Capture Time via Binary Input
F.No. Alarm Comments
963 IL1dmd= I L1 demand
964 IL2dmd= I L2 demand
965 IL3dmd= I L3 demand
833 I1dmd = I1 (positive sequence) Demand
834 Pdmd = Active Power Demand
1052 Pdmd Forw= Active Power Demand Forward
1053 Pdmd Rev = Active Power Demand Reverse
835 Qdmd = Reactive Power Demand
1054 Qdmd Forw= Reactive Power Demand Forward
1055 Qdmd Rev = Reactive Power Demand Reverse
836 Sdmd = Apparent Power Demand
F.No. Alarm Comments
395 >I MinMax Reset >I MIN/MAX Buffer Reset
396 >I1 MiMaReset >I1 MIN/MAX Buffer Reset
397 >U MiMaReset >U MIN/MAX Buffer Reset
398 >UphphMiMaRes >Uphph MIN/MAX Buffer Reset