Functions
6-1357SA6 Manual
C53000-G1176-C156-2
6.7.3 Settings
Note: The indicated secondary current values for setting ranges and default settings
refer to I
N
= 1 A. For the nominal current 5 A the current values are to be multiplied
by 5.
Addresses which have an „A“ attached to its end can only be changed with DIGSI
®
4
in
Additional Settings“.
Addr. Setting Title Setting Options Default Setting Comments
3101 FCT EarthFltO/C ON
OFF
ON Earth Fault overcurrent function
is
3102 BLOCK for Dist. with every Pickup
with single-phase Pickup
with multi-phase Pickup
NO
with every Pickup Block E/F for Distanceprotection
3103 BLOCK 1pDeadTim YES
NO
YES Block E/F for 1pole Dead time
3104A Iph-STAB. Slope 0..30 % 10 % Stabilisation Slope with Iphase
3105 3IoMin Teleprot 0.01..1.00 A 0.50 A 3Io-Min threshold for Teleprot.
schemes
3105 3IoMin Teleprot 0.003..1.000 A 0.500 A 3Io-Min threshold for Teleprot.
schemes
3170 2nd InrushRest 10..45 % 15 % 2nd harmonic ratio for inrush
restraint
3171 Imax InrushRest 0.50..25.00 A 7.50 A Max.Current, overriding inrush
restraint
3172 SOTF Op. Mode with Pickup (non-directional)
with Pickup and direction
with Pickup and
direction
Instantaneous mode after Swit-
chOnToFault
3173 SOTF Time DELAY 0.00..30.00 sec 0.00 sec Trip time delay after SOTF
3110 Op. mode 3I0>>> Forward
Reverse
Non-Directional
Inactive
Inactive Operating mode
3111 3I0>>> 0.50..25.00 A 4.00 A 3I0>>> Pickup
3112 T 3I0>>> 0.00..30.00 sec; 0.30 sec T 3I0>>> Time delay
3113 3I0>>> Telep/BI NO
YES
NO Instantaneous trip via Teleprot./
BI
3114 3I0>>>SOTF-Trip NO
YES
NO Instantaneous trip after Swit-
chOnToFault
3115 3I0>>>InrushBlk NO
YES
NO Inrush Blocking
3120 Op. mode 3I0>> Forward
Reverse
Non-Directional
Inactive
Inactive Operating mode
3121 3I0>> 0.20..25.00 A 2.00 A 3I0>> Pickup
3122 T 3I0>> 0.00..30.00 sec; 0.60 sec T 3I0>> Time Delay

Table of Contents

Other manuals for Siemens siprotec 7SA6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA6 and is the answer not in the manual?

Siemens siprotec 7SA6 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA6
CategoryRelays
LanguageEnglish

Related product manuals