Page #34 background imageLoading...
Page #34 background image
Hardware and Connections
2-2
7SA6 Manual
C53000-G1176-C156-2
2.1 Version of 7SA6 for Panel Flush Mounting (Cubicle Mounting)
The numerical Distance Protection SIPROTEC
®
7SA6 for panel and cubicle flush
mounting is enclosed in a 7XP20 housing. 3 housing sizes are available, namely
1
/
3
,
1
/
2
and
1
/
1
(of 19 inch).
Housing size
1
/
3
is provided with a four-line display. The two other housing sizes can
either be ordered with a four-line display or a graphic display.
Different termination techniques are available depending on the ordered version.
2.1.1 Housing
The housing consists of a rectangular tube with a rear plate and a front cover. Guide
rail mats are mounted at the top and bottom on the inside of the tube, to guide the
modules during mounting. Each guide rail mat has visible numbering from 1 to 42, des-
ignating the mounting positions of the modules. The modules and the front cover are
connected by means of flat ribbon cables and the corresponding plug connectors. The
rear plate screwed to the tube contains the required connectors for the external con-
nections to the device.
The front cover can be taken off after removal of the covers located at the 4 corners
of the front cover and the 4 screws that are then revealed. Housing size
1
/
1
has 2 ad-
ditional screw covers located at the centre of the top and bottom of the front cover
frame; accordingly 6 screws must be removed in this case. The front cover has a
membrane keypad containing the control and indication elements required for the user
interface with the device. All terminations to the control and indication elements are
combined by a converter module on the front cover, and routed to the processor mod-
ule (CPU) via a plug connector.
The name plate containing the principal data of the device, such as auxiliary supply
voltage, the rated test voltage and the ordering code (MLFB) is located on the external
top of the housing and on the inside of the front cover.
The mechanical dimension drawings are located in Section 10.22.

Table of Contents

Other manuals for Siemens siprotec 7SA6