Functions
6-272 7SA6 Manual
C53000-G1176-C156-2
Settings:
Address
5032 20 mA (D2) = 20000 A,
Address
5039 Tmax OUTPUT(D2) = 5.00 s.
6.20.3 Settings
Addr. Setting Title Setting Options Default Setting Comments
5001 20 mA (B1) = 10.0..1000.0 % 200.0 % 20 mA (B1) correspond to
5002 20 mA (B1) = 10..100000 A 20000 A 20 mA (B1) correspond to
5003 20 mA (B1) = 1.0..1000.0 km 50.0 km 20 mA (B1) correspond to
5004 20 mA (B1) = 1.0..1000.0 Miles 50.0 Miles 20 mA (B1) correspond to
5006 MIN VALUE (B1) 0.0..5.0 mA 4.0 mA Output value (B1) valid from
5007 NEG VALUE (B1) 1.00..22.50 mA 19.84 mA Output value (B1) for negative
values
5008 OVERFLOW (B1) 1.00..22.50 mA 22.50 mA Output value (B1) for overflow
5009 Tmax OUTPUT(B1) 0.10..180.00 sec; 5.00 sec Maximum output time (B1)
5011 20 mA (B2) = 10.0..1000.0 % 200.0 % 20 mA (B2) correspond to
5012 20 mA (B2) = 10..100000 A 20000 A 20 mA (B2) correspond to
5013 20 mA (B2) = 1.0..1000.0 km 50.0 km 20 mA (B2) correspond to
5014 20 mA (B2) = 1.0..1000.0 Miles 50.0 Miles 20 mA (B2) correspond to
5016 MIN VALUE (B2) 0.0..5.0 mA 4.0 mA Output value (B2) valid from
5017 NEG VALUE (B2) 1.00..22.50 mA 19.84 mA Output value (B2) for negative
values
5018 OVERFLOW (B2) 1.00..22.50 mA 22.50 mA Output value (B2) for overflow
5019 Tmax OUTPUT(B2) 0.10..180.00 sec; 5.00 sec Maximum output time (B2)
5021 20 mA (D1) = 10.0..1000.0 % 200.0 % 20 mA (D1) correspond to
5022 20 mA (D1) = 10..100000 A 20000 A 20 mA (D1) correspond to
5023 20 mA (D1) = 1.0..1000.0 km 50.0 km 20 mA (D1) correspond to
5024 20 mA (D1) = 1.0..1000.0 Miles 50.0 Miles 20 mA (D1) correspond to
5026 MIN VALUE (D1) 0.0..5.0 mA 4.0 mA Output value (D1) valid from
5027 NEG VALUE (D1) 1.00..22.50 mA 19.84 mA Output value (D1) for negative
values
5028 OVERFLOW (D1) 1.00..22.50 mA 22.50 mA Output value (D1) for overflow
5029 Tmax OUTPUT(D1) 0.10..180.00 sec; 5.00 sec Maximum output time (D1)
5031 20 mA (D2) = 10.0..1000.0 % 200.0 % 20 mA (D2) correspond to
5032 20 mA (D2) = 10..100000 A 20000 A 20 mA (D2) correspond to

Table of Contents

Other manuals for Siemens siprotec 7SA6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA6 and is the answer not in the manual?

Siemens siprotec 7SA6 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA6
CategoryRelays
LanguageEnglish

Related product manuals