Functions
6-3097SA6 Manual
C53000-G1176-C156-2
Remote Measured
Values
During communication, the data of the other ends of the protected object can also be
read out. For each of the devices, the currents and voltages involved as well as phase
shifts between the local and transfer measured quantities can be displayed. This is
especially helpful for checking the correct and coherent phase allocation at the
differrent line ends. Furthermore, the device addresses of the other devices is
transmittedsothatallimportantdataofallendsareavailableinthesubstation.All
possible data are listed in Table 6-18.
S, P, Q apparent, real, and reactive pow-
er
MVA,
MW,
MVAR
3·U
N
·I
N
rated operational values
1
)
2
)
cos
ϕ power factor (abs) (abs)
f frequency Hz Hz rated frequency
Θ
L1
/Θ
trip
, Θ
L2
/Θ
trip
,
Θ
L3
/Θ
trip
thermal value of each line
relatedtotripvalue
overtemperature
Θ/Θ
trip
thermal value, related to trip val-
ue,
calculated acc. to the configured
method
overtemperature
U
line
,U
sync
,U
diff
line voltage, busbar voltage and
voltage magnitude difference (for
synchro-check)
kV
f
line
,f
sync
,f
diff
line voltage, busbar voltage and
frequency difference (for synchro-
nism check)
Hz
ϕ
diff
magnitude of the phase angle dif-
ference between line and busbar
(for sychronism check)
°—
I
EEa
,I
EEr
active and reactive component of
earth fault current
AmA
Table 6-17 Operational measured values
Measured values primary secondary % referred to
1
) acc. to address 1104 (refer to Sub-section 6.1.3)
2
) acc. to address 1103 (refer to Sub-section 6.1.3)
3
) with consideration of the factor 221 I4/Iph CT (refer to Sub-section 6.1.1)
Tabelle 6-18 Operational measured values transmitted from the other ends and compared
with the local values
Data
% referring to
Device ADR Device address of the remote device (absolute)
I
L1
,I
L2
,I
L3
Phase currents of the remote device Rated oper. current
1
)
I
L1
,I
L2
,I
L3
local Phase currents of the local device Rated oper. current
1
)
ϕ(I
L1
), ϕ(I
L2
), ϕ(I
L3
) Phase angles between the remote
and the local phase currents
°
1
) for lines according to address 1104 (see Section 6.1.3)
2
) according to address 1103 (see Section 6.1.3)

Table of Contents

Other manuals for Siemens siprotec 7SA6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA6 and is the answer not in the manual?

Siemens siprotec 7SA6 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA6
CategoryRelays
LanguageEnglish

Related product manuals