Application macros 111
Summary of the I/O connections of the application macros
The following table gives the summary of the default I/O connections of all application
macros.
Input/
output
Macro
ABB
standard
3-wire Alternate Motor
potentiom.
Hand/Auto PID
control
Torque
control
AI1
(0…10 V)
Freq. ref. Speed ref. Speed ref. - Speed ref.
(Hand)
Speed ref.
(Hand) /
Proc. ref.
(PID)
Speed ref.
(Speed)
AI2
(0…20 mA)
----Speed ref.
(Auto)
Process
value
Torque
ref.
(Torque)
AO Output
freq.
Speed Speed Speed Speed Speed Speed
DI1 Stop/Start Start
(pulse)
Start (fwd) Stop/Start Stop/Start
(Hand)
Stop/Start
(Hand)
Stop/Start
(Speed)
DI2 Fwd/Rev Stop
(pulse)
Start (rev) Fwd/Rev Fwd/Rev
(Hand)
Hand/PID Fwd/Rev
DI3 Const.
speed
input 1
Fwd/Rev Const.
speed
input 1
Speed ref.
up
Hand/Auto Const.
speed 1
Speed/
Torque
DI4 Const.
speed
input 2
Const.
speed
input 1
Const.
speed
input 2
Speed ref.
down
Fwd/Rev
(Auto)
Run
enable
Const.
speed 1
DI5 Ramp pair
selection
Const.
speed
input 2
Ramp pair
selection
Const.
speed 1
Stop/Start
(Auto)
Stop/Start
(PID)
Ramp pair
selection
RO Fault (-1) Fault (-1) Fault (-1) Fault (-1) Fault (-1) Fault (-1) Fault (-1)
DO Fault (-1) Fault (-1) Fault (-1) Fault (-1) Fault (-1) Fault (-1) Fault (-1)