Program features 147
Settings
Parameter 3023 WIRING FAULT
Input phase loss
Input phase loss protection circuits supervise the input power cable connection status
by detecting intermediate circuit ripple. If a phase is lost, the ripple increases.
Settings
Parameter 3016 SUPPLY PHASE
Pre-programmed faults
Overcurrent
The overcurrent trip limit for the drive is 325% of the drive nominal current.
DC overvoltage
The DC overvoltage trip limit is 420 V (for 200 V drives) and 840 V (for 400 V drives).
DC undervoltage
The DC undervoltage trip limit is adaptive. See parameter 2006 UNDERVOLT CTRL.
Drive temperature
The drive supervises the IGBT temperature. There are two supervision limits: Alarm
limit and fault trip limit.
Short circuit
If a short circuit occurs, the drive will not start and a fault indication is given.
Internal fault
If the drive detects an internal fault, the drive is stopped and a fault indication is given.
Operation limits
The drive has adjustable limits for speed, current (maximum), torque (maximum) and
DC voltage.
Settings
Parameter group 20 LIMITS

Table of Contents

Other manuals for ABB ACS355

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS355 and is the answer not in the manual?

ABB ACS355 Specifications

General IconGeneral
Input Voltage200 V to 240 V AC, 380 V to 480 V AC
Frequency47 Hz to 63 Hz
Control MethodScalar control
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short circuit
Communication InterfacesModbus RTU, CANopen
Enclosure RatingIP20
Operating Temperature-10°C to +50°C (14°F to 122°F)
Storage Temperature-40°C to +70°C (-40 to +158 °F)
Humidity95% RH (non-condensing)
AltitudeUp to 1000 m (3280 ft) without derating

Related product manuals