82 Control panels
Parameter mode
In the Parameter mode, you can:
view and change parameter values
select and modify the signals shown in the Output mode
start, stop, change the direction and switch between local and remote control.
How to select a parameter and change its value
Step Action Display
1. Go to the Main menu by pressing if you are in
the Output mode, otherwise by pressing
repeatedly until you see MENU at the bottom.
2. If the panel is not in the Parameter mode (“PAr” not
visible), press key or until you see “PAr”
and then press . The display shows the number
of one of the parameter groups.
3. Use keys and to find the desired
parameter group.
4. Press . The display shows one of the
parameters in the selected group.
5. Use keys and to find the desired
parameter.
6. Press and hold for about two seconds until the
display shows the value of the parameter with
underneath indicating that changing of the value is
now possible.
Note: When is visible, pressing keys and
simultaneously changes the displayed value to
the default value of the parameter.
7. Use keys and to select the parameter
value. When you have changed the parameter value,
starts flashing.
To save the displayed parameter value, press
.
To cancel the new value and keep the original,
press .
LOC
MENU FWD
rEF
LOC
MENU FWD
PAr
LOC
PAR FWD
-01-
LOC
PAR FWD
-11-
LOC
PAR FWD
1101
LOC
PAR FWD
1103
SET
SET
LOC
PAR SET FWD
1
SET
LOC
PAR SET FWD
2
LOC
PAR FWD
1103

Table of Contents

Other manuals for ABB ACS355

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS355 and is the answer not in the manual?

ABB ACS355 Specifications

General IconGeneral
Input Voltage200 V to 240 V AC, 380 V to 480 V AC
Frequency47 Hz to 63 Hz
Control MethodScalar control
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short circuit
Communication InterfacesModbus RTU, CANopen
Enclosure RatingIP20
Operating Temperature-10°C to +50°C (14°F to 122°F)
Storage Temperature-40°C to +70°C (-40 to +158 °F)
Humidity95% RH (non-condensing)
AltitudeUp to 1000 m (3280 ft) without derating