Program features 149
Parameter lock
The user can prevent parameter adjustment by activating the parameter lock.
Settings
Parameters 1602 PARAMETER LOCK and 1603 PASS CODE
PID control
There are two built-in PID controllers in the drive:
Process PID (PID1) and
External/Trim PID (PID2).
The PID controller can be used when the motor speed needs to be controlled based
on process variables such as pressure, flow or temperature.
When the PID control is activated, a process reference (setpoint) is connected to the
drive instead of a speed reference. An actual value (process feedback) is also
brought back to the drive. The drive compares the reference and the actual values,
and automatically adjusts the drive speed in order to keep the measured process
quantity (actual value) at the desired level (reference).
The control operates on a 2 ms time level.
Process controller PID1
PID1 has two separate sets of parameters (40 PROCESS PID SET 1, 41 PROCESS
PID SET 2). Selection between parameter sets 1 and 2 is defined by a parameter.
In most cases when there is only one transducer signal wired to the drive, only
parameter set 1 is needed. Two different parameter sets (1 and 2) are used eg when
the load of the motor changes considerably in time.
External/Trim controller PID2
PID2 (42 EXT / TRIM PID) can be used in two different ways:
External controller: Instead of using additional PID controller hardware, the user
can connect PID2 output through drive analog output or fieldbus controller to
control a field instrument like a damper or a valve.
Trim controller: PID2 can be used to trim or fine tune the reference of the drive.
See section Reference trimming on page 129.

Table of Contents

Other manuals for ABB ACS355

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS355 and is the answer not in the manual?

ABB ACS355 Specifications

General IconGeneral
Input Voltage200 V to 240 V AC, 380 V to 480 V AC
Frequency47 Hz to 63 Hz
Control MethodScalar control
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short circuit
Communication InterfacesModbus RTU, CANopen
Enclosure RatingIP20
Operating Temperature-10°C to +50°C (14°F to 122°F)
Storage Temperature-40°C to +70°C (-40 to +158 °F)
Humidity95% RH (non-condensing)
AltitudeUp to 1000 m (3280 ft) without derating

Related product manuals